Chapter 3: Configuration and Parameters
Page 3–37
Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
p
arameTer
d
eTails
– “a
dvanCed
” m
enu
of
p
arameTers
(
ConTinued
)
P8.6 –
Stop Current Limit Trip
Hold. Reg. Type:
Description:
Read/Write
Selects between trip or continue if the stop current limit has been active for too long.
Range:
Modbus Decimal Value: Default (decimal):
• Off : The stop will continue regardless of the motor current
level.
• On : The SR55 will trip. This trip is constrained by the Stop
Current Limit Level and the Stop Current Limit Time.
• 0
• 1
• Off (0)
Modbus Address:
Modbus Format:
53791 ( D21F hex )
16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Trip Settings → Stop Current Limit Trip
(also Home → Advanced → Stop Settings → Stop Current Limit → Stop Current Limit Trip)
P8.7 –
PTC Motor Thermistor Trip
Hold. Reg. Type:
Description:
Read/Write
A single PTC motor thermistor or set of PTC motor thermistors can be connected to the PTC
terminals.
Range:
Modbus Decimal Value: Default (decimal):
• Off : The SR55 will continue to operate.
• On : The SR55 will trip if the motor thermistor exceeds its
response temperature, or the PTC input is open circuit (> 4kΩ).
• 0
• 1
• Off (0)
Modbus Address:
Modbus Format:
53794 ( D222 hex )
16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Trip Settings → PTC Motor Thermistor Trip
(also Home → I/O → PTC Motor Thermistor Trip)
P8.8 –
L1-L2-L3 Trip
Hold. Reg. Type:
Description:
Read/Write
Determines if supply phase sequence is incorrect for motor rotation.
Range:
Modbus Decimal Value: Default (decimal):
• Off : The SR55 will continue to operate normally.
• On : Trips if the phase sequence is L1, L2, L3.
• 0
• 1
• Off (0)
Modbus Address:
Modbus Format:
53808 ( D230 hex )
16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Trip Settings → L1-L2-L3 Trip
P8.9 –
L1-L3-L2 Trip
Hold. Reg. Type:
Description:
Read/Write
Determines if supply phase sequence is incorrect for motor rotation.
Range:
Modbus Decimal Value: Default (decimal):
• Off : The SR55 will continue to operate normally.
• On : Trips if the phase sequence is L1, L3, L2.
• 0
• 1
• Off (0)
Modbus Address:
Modbus Format:
53807 ( D22F hex )
16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Trip Settings → L1-L3-L2 Trip
Summary of Contents for Stellar SR55 Series
Page 1: ...Stellar SR55 Soft Starter User Manual SR55_UMW First Edition Revision F...
Page 2: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 6: ...Page W 4 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 8: ...Page H 2 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 201: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 202: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019...