Page 3–10
Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 3: Configuration and Parameters
Parameter Summary for Touchscreen Setup – “I/O” Category (continued)
– Group
Parameter
Units Range
Read /
Write
Modbus
Default
Setting
User
Setting
PNU
Hex
Cat
egor
y – I/O
(P13)
Analog
Outputs
[detailed
info starts
]
P13�0 – Analog Output Type
toggle
0–10V / 4–20mA
R/W
8960
2300
0–10V
P13�1 – Select Function
–
Off
Current Measured
Overload
Overload SCR
P-Total
R/W
9024
2340
OFF
P13�2 – Scaling Level
–
0 to 16,384
R/W
9088
2380
0
(P14)
[details
]
P14�0 – PTC Motor Thermistor Trip
toggle
OFF / ON
R/W
53794
D222 OFF
p
arameTers
from
“m
oniTor
” m
enu
C
aTegory
– s
ummary
Summary – Parameters for Touchscreen Setup – “Monitor” Category
Cat
egor
y – Monit
or
Group
Parameter
Units Range
Read /
Write
Modbus
Default
Setting
User
Setting
Address Hex
(P15)
Monitoring
[detailed info
starts
P15�0 – Line Frequency
Hz
45 to 65
Read
32000
7D00 n/a
–
P15�1 – Phase Rotation
–
L1-L2-L3 or L1-L3-L2
Read
32064
7D40 L1-L2-L3
–
P15�2 – I1
A
0 to 10,000
Read
33536
8300
0
–
P15�3 – I2
A
0 to 10,000
Read
33538
8302
0
–
P15�4 – I3
A
0 to 10,000
Read
33540
8304
0
–
P15�5 – Current I rms
A
0 to 10,000
Read
32896
8080
0
–
P15�6 – V rms (Approx)
V
0 to 500
Read
32960
80C0
0
–
P15�7 – Real Power Factor
–
0 to 1
Read
33024
8100
0
–
P15�8 – True Power P
kW
0 to 10,000
Read
34688
8780
0
–
P15�9 – Apparent Power S
kVA
0 to 10,000
Read
34816
8800
0
–
P15�10 – Reactive Power Q
kVAR
0 to 10,000
Read
34944
8880
0
–
P15�11 – iERS Saving Level
%
0 to 100
Read
35008
88C0
0
–
P15�12 – Delay Angle
degree
0° to 55°
Read
22400
5780
0
–
P15�13 – Backstop
degree
0° to 55°
Read
23040
5A00
0
–
P15�14 – Delay Max
degree
0° to 55°
Read
22464
57C0
0
–
P15�15 – Pres PF Degrees
degree
0° to 90°
Read
21824
5540
0
–
P15�16 – Ref PF Degrees
degree
0° to 90°
Read
21760
5500
0
–
P15�17 – Start Saving Level
%
50% to 80% of mtr FLA
Read
21320
5348
80%
–
P18�0 – Last Peak (Start) Current
A
0 to 10,000
Read
38400
9600
0
–
P15�18 – HeatSink Temp
°C
-20°C to 80°C
Read
36544
8EC0
ambient
–
P15�19 – Motor Thermistor
–
0 to 1024
Read
10432
28C0
0
–
P15�20 – Overload
%
0 to 100
Read
33408
8280
0
–
Summary of Contents for Stellar SR55 Series
Page 1: ...Stellar SR55 Soft Starter User Manual SR55_UMW First Edition Revision F...
Page 2: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 6: ...Page W 4 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 8: ...Page H 2 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 201: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 202: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019...