Chapter 3: Configuration and Parameters
Page 3–51
Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
p
arameTer
d
eTails
– “i/o” m
enu
of
p
arameTers
(
ConTinued
)
P12.2 –
Analog Input: Scaling Level
Type:
Description:
Read/Write
Allows the selected function to be scaled. The selected function will change in proportion with
the input.
• The function will be at its “Scaling Level” when the input is at its maximum.
Range:
Modbus Decimal Value:
Default:
0 – 16384
linear scale ( 1 = 0.006104 % )
0% – 100% = (0 – 16384)
x% / 0.006104% = Modbus dec. value
EX: Modbus value of 5250 = 32.05%
16384
Modbus Address:
Modbus Format:
9728 ( 2600 hex )
16-bit unsigned
Touchscreen Menu Path:
Home → I/O → Analog Inputs → Scaling Level
i/o “a
nalog
o
uTpuT
” p
arameTers
P13.0 –
Analog Output Type
Hold. Reg. Type:
Description:
Read/Write
Defines the function of the Analog Output (AO).
Range:
Modbus Decimal Value: Default (decimal):
• 0–10V : The output voltage varies from 0 to 10V.
• 4–20mA : The output varies from 4 to 20mA.
• 0
• 1
• 0–10V (0)
Modbus Address:
Modbus Format:
8960 ( 2300 hex )
16-bit unsigned
Touchscreen Menu Path:
Home → I/O → Analog Outputs → Analog Output Type
P13.1 –
Analog Output: Select Function
Hold. Reg. Type:
Description:
Read/Write
Allows the Analog Output to be mapped to different functions. The output will change in
proportion with the selected function.
• By default the output will be at a maximum when the selected function equals its max value.
Range:
Modbus Decimal Value:
Default (decimal):
• Off
• Current Measured
• Overload
• Overload SCR
• P-Total
• 0
• 514
• 522
• 161
• 542
• Off (0)
Modbus Address:
Modbus Format:
9024 ( 2340 hex )
16-bit unsigned
Touchscreen Menu Path:
Home → I/O → Analog Outputs → Select Function (Analog Output)
Examples of P13.1 Analog Output Fuction Selections
AO Function
Settings:
Modbus
Dec. Value: Example:
Current
Measured
514
AO shows P15.5 Current I
rms
. Ex: This value can be fed out to a panel
ammeter for panel designs, or can be used as feedback to a PLC
system for monitoring or management system such as SCADA, etc.
Overload
522
AO shows P15.20 Overload. Ex: This value can be fed back to a PLC
system for monitoring or management system such as SCADA, etc.
P-Total
542
AO shows P15.8 True Power P. Ex: This value can be fed out to a panel
power meter for panel designs, or can be used as feedback to a PLC
system for monitoring or management system such as SCADA, etc.
Summary of Contents for Stellar SR55 Series
Page 1: ...Stellar SR55 Soft Starter User Manual SR55_UMW First Edition Revision F...
Page 2: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 6: ...Page W 4 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 8: ...Page H 2 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 201: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 202: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019...