Appendix D: Sizing an SR55 Soft Starter
Page D–5
Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
I
NcReAsed
s
TARTs
peR
h
ouR
– d
eRATING
If more than the standard number of starts/hour is required, the SR55 must be derated. To
derate for more starts/hour, the motor full load current must be less than the SR55 current.
The relationship between the SR55 deration and the starts/hour is given below in Figure 2 and
the two examples that follow. This assumes that the SR55 is still operating at the same duty
(F) as given in Figure 1.
Figure 2: SR55 Starts/Hour Deration
Deration Curve
Starts/Hour Deration Factor
0.5
0.55
0.6
0.65
0.7
0.75
0.8
0.85
10
15
20
25
30
35
40
D
er
at
io
n
Fa
ct
or
[ M
ot
or
F
ul
l L
oa
d
Cu
rr
en
t
/
SR55
C
ur
re
nt
]
Starts / Hour
10
083
15
073
20
066
25
061
30
056
35
053
40
050
Deration Factor = (138 - (24·ln(starts/hr))) / 100
[where ln(starts/hr) is the natural log of the # of starts/hour]
Example: Deration Factor for 10 starts/hr = (138 - (24·ln(10))) / 100 = 0.83
Summary of Contents for Stellar SR55 Series
Page 1: ...Stellar SR55 Soft Starter User Manual SR55_UMW First Edition Revision F...
Page 2: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 6: ...Page W 4 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 8: ...Page H 2 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 201: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 202: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019...