Chapter 5: Communications
Page 5–17
Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
e
Ther
n
eT
/ip n
eTWork
C
ommuniCaTions
(
ConTinued
)
C
onneCTing
To
The
sr55-Cm-eneT m
odule
Through
e
xpliCiT
m
essage
:
There are a few different objects that can be read or be written to via Explicit Messaging:
Objects Supported By Explicit Messaging
Description
Read Only? Service
Class
Instance
Attribute
Run
No
16 (0x10)
41 (0x29)
1
3
Fault Reset
No
16 (0x10)
41 (0x29)
1
12 (0x0c)
Network Control
No
16 (0x10)
41 (0x29)
1
5
Faulted
Yes
14 (0x0e)
41 (0x29)
1
10 (0x0a)
Warning
Yes
14 (0x0e)
41 (0x29)
1
11 (0x0b)
Running Forward
Yes
14 (0x0e)
41 (0x29)
1
7
Ready
Yes
14 (0x0e)
41 (0x29)
1
9
Control from Network
Yes
14 (0x0e)
41 (0x29)
1
15 (0x0f)
Drive State
Yes
14 (0x0e)
41 (0x29)
1
6
With the exception of the “Drive State” parameter, all of the other parameters either require a
value of 1 or 0 for SET (16), and will return a value of 0 or 1 on the GET (14) parameters.
To run the starter, a value of 1 must be set in the “Network Control” parameter first and then a
value of 1 can be sent to the “Run” parameter to start the motor and a value of 0 to the same
parameter to stop the motor.
If the Communications Trip parameter is enabled, a message must be sent to the starter at
a faster rate than what is configured for the Timeout parameter. It is typical in this situation
to poll the “Faulted” parameter to view the state of the starter along with keeping the
Communications Trip from enabling and stopping the motor.
If communications are interrupted for a long enough period to invoke the Communications
Trip fault, the following sequence is required to restart the motor:
•
Send a 0 to the “Run” parameter
•
Send a 1 to the “Fault Reset” parameter
•
Send a 0 to the “Fault Reset” parameter
•
Now you can restart the motor by sending a 1 to the “Run” parameter
Summary of Contents for Stellar SR55 Series
Page 1: ...Stellar SR55 Soft Starter User Manual SR55_UMW First Edition Revision F...
Page 2: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 6: ...Page W 4 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...