Byte 16: Fault 2
The fault signals contain the causes why the actuator cannot be operated.
Table 13: Byte 16: Fault 2
Description
Value
Prm-Text-Def GSD file
Designation
(process representation)
Bit
No signal (reserved)
—
—
0
No signal (reserved)
—
—
1
No signal (reserved)
—
—
2
No signal (reserved)
—
—
3
No signal (reserved)
—
—
4
No signal
—
5
Configuration error of REMOTE interface active.
1
(123) = "Bit: Config error
remote"
Config. error REMOTE
6
No signal.
0
The phase conductors L1, L2 and L3 are connected in
the wrong sequence.
1
(58) = "Bit: Wrong phase
sequence"
Incorrect phase seq
7
Phase sequence is ok.
0
Byte 17: Warnings 1
The warning signals are for information only and do not interrupt or disable an
operation (as opposed to faults).
Table 14: Byte 17: Warnings 1
Description
Value
Prm-Text-Def GSD file
Designation
(process representation)
Bit
No signal (reserved)
—
—
0
No signal (reserved)
—
—
1
No signal (reserved)
—
—
2
No signal
—
FQM fail safe flt
3
Warning: Limit value for Torque warning CLOSE ex-
ceeded
1
(125) = "Bit: Torque wrn
CLOSE"
Torque wrn CLOSE
4
No signal
0
Warning: Limit value for Torque warning OPEN exceeded
1
(124) = "Bit: Torque wrn
OPEN"
Torque wrn OPEN
5
No signal
0
Warning: A SIL fault of the SIL sub-assembly has oc-
curred.
1
(206) = "SIL fault"
SIL fault
1)
6
No signal
0
Warning: No actuator reaction to operation commands
within the set reaction time.
1
(71) = "Bit: No reaction"
Wrn no reaction
7
No signal
0
The safety function indications via fieldbus are for information only and must not be used as part of a safety function. The I/O signals of
the SIL module must be used for this purpose.
1)
Byte 18: Warnings 2
Table 15: Byte 18: Warnings 2
Description
Value
Prm-Text-Def GSD file
Designation
(process representation)
Bit
Warning: Temperature within controls housing too high
1
(88) = "Bit: WrnControl-
sTemp"
Wrn controls temp.
0
No signal
0
No signal (reserved)
—
—
1
No signal (reserved)
—
—
2
The external 24 V DC voltage supply of the controls has
exceeded the power supply limits.
1
(68) = "Bit: 24 V DC, extern-
al"
24 V DC external
3
No signal
0
29
Actuator controls
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Description of the data interface
Summary of Contents for AC(V) 01.2
Page 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Page 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Page 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Page 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...