Table 30: Operation commands via byte 6 for activated multiport valve function
Behaviour
≙
Operation direction/posi-
tion
Value
Position 1 is approached selecting the shortest
path
Position 1
0x01
Position 2 is approached selecting the shortest
path
Position 2
0x02
Position 3 is approached selecting the shortest
path
Position 3
0x04
Position 4 is approached selecting the shortest
path
Position 4
0x08
Position 5 is approached selecting the shortest
path
Position 5
0x10
Position 6 is approached selecting the shortest
path
Position 6
0x20
Position 7 is approached selecting the shortest
path
Position 7
0x40
Position 8 is approached selecting the shortest
path
Position 8
0x80
Position 9 is approached selecting the shortest
path
Position 9
0x81
Position 10 is approached selecting the shortest
path
Position 10
0x82
Position 11 is approached selecting the shortest
path
Position 11
0x83
Position 12 is approached selecting the shortest
path
Position 12
0x84
Actuator operates in clockwise direction (without
stop at any position)
CW
0x90
Position 1 is approached in clockwise direction
(CW).
CW Position 1
0x91
Position 2 is approached in clockwise direction
(CW).
CW Position 2
0x92
Position 3 is approached in clockwise direction
(CW).
CW Position 3
0x93
Position 4 is approached in clockwise direction
(CW).
CW Position 4
0x94
Position 5 is approached in clockwise direction
(CW).
CW Position 5
0x95
Position 6 is approached in clockwise direction
(CW).
CW Position 6
0x96
Position 7 is approached in clockwise direction
(CW).
CW Position 7
0x97
Position 8 is approached in clockwise direction
(CW).
CW Position 8
0x98
Position 9 is approached in clockwise direction
(CW).
CW Position 9
0x99
Position 10 is approached in clockwise direction
(CW).
CW Position 10
0x9A
Position 11 is approached in clockwise direction
(CW).
CW Position 11
0x9B
Position 12 is approached in clockwise direction
(CW).
CW Position 12
0x9C
Actuator operation in counterclockwise direction
(without stop at any position)
CCW
0xA0
Position 1 is approached in counterclockwise direc-
tion (CCW).
CCW Position 1
0xA1
Position 2 is approached in counterclockwise direc-
tion (CCW).
CCW Position 2
0xA2
39
Actuator controls
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Description of the data interface
Summary of Contents for AC(V) 01.2
Page 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Page 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Page 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Page 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...