Byte 2: Actuator signals
Table 5: Byte 2: Actuator signals
Description
Value
Prm-Text-Def GSD file
Designation
(process representation)
Bit
Motor protection tripped
1
(56) = "Bit: Thermal fault"
Thermal fault
0
No signal
0
●
When connecting to a 3-ph AC system and with in-
ternal 24 V DC supply of the electronics: Phase 2 is
missing.
●
When connecting to a 3-ph or 1-ph AC system and
with external 24 V DC supply of the electronics: One
of the phases L1, L2 or L3 is missing.
1
(57) = "Bit: Phase fault"
Phase fault
1
All phases are available.
0
Selector switch is in position REMOTE.
1
(9) = "Bit: Sel. sw. RE-
MOTE"
Selector sw. REMOTE
2
Selector switch is not in position REMOTE.
0
Selector switch is in position LOCAL.
1
(8) = "Bit: Selector sw.
LOCAL"
Selector sw. LOCAL
3
Selector switch is not in position LOCAL.
0
Limit switch operated in end position OPEN
1
(12) = "Bit: Limit sw. OPEN"
Limit switch OPEN
4
No signal
0
Limit switch operated in end position CLOSED
1
(11) = "Bit: Limit sw.
CLOSED"
Limit switch CLOSED
5
No signal
0
Torque switch operated in direction OPEN.
1
(14) = "Bit: Torque sw.
OPEN"
Torque sw. OPEN
6
No signal
0
Torque switch operated in direction CLOSE.
1
(13) = "Bit: Torque sw.
CLOSE"
Torque sw. CLOSED
7
No signal
0
Bytes 3 and 4: Actual position
Byte 3 = high byte, byte 4 = low byte.
If a position transmitter (potentiometer, RWG, EWG, or MWG) is installed in the
actuator, bytes 3 and 4 are used to transmit the current actuator position. The value
is transmitted in per mil (value: 0 – 1,000).
Byte 5: Device status
Table 6: Byte 5: Device status
Description
Value
Prm-Text-Def GSD file
Designation
(process representation)
Bit
Collective signal 04:
Contains the result of a disjunction (OR-operation) of all
bits comprised in bytes 13 and 14 (Not ready REMOTE
1 and Not ready REMOTE 2).
The actuator cannot be operated from REMOTE.
The actuator can only be operated via the local controls.
1
(22) = "Bit: Not ready RE-
MOTE"
Not ready REMOTE
0
In bytes 13 and 14, no signals are active (all bits are set
to 0).
0
Collective signal 02:
Contains the result of a disjunction (OR-operation) of all
bits of bytes 17 to 20 (Warning 1 to Warning 4).
1
(21) = "Bit: Warnings"
Warning
1
In bytes 17 and 20, no warnings are active (all bits are
set to 0).
0
Collective signal 03:
Contains the result of a disjunction (OR-operation) of all
bits of bytes 15 and 16 (Fault 1 and Fault 2).
The actuator cannot be operated.
1
(20) = "Bit: Fault"
Fault
2
In bytes 15 and 16, no faults are active (all bits are set to
0).
0
24
Actuator controls
Description of the data interface
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Summary of Contents for AC(V) 01.2
Page 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Page 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Page 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Page 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...