Byte 9 and byte 10: Input AIN 1
Byte 9 = high byte, byte 10 = low byte.
Bytes 9 and 10 transmit the value of the first additional free analogue current input
of the Profibus DP interface. The start and end values can be set at the AC via push
buttons and display. (For operation, please refer to the respective operation
instructions for the actuator.)
If the measuring values are 0.3 mA below the initial value, a signal loss is indicated.
The value is transmitted in per mil (value: 0 – 1,000).
Byte 11 and byte 12: Torque
Byte 11 = high byte, byte 12 = low byte.
Bytes 11 and 12 transmit the current torque of the actuator (only if an MWG is installed
in the actuator).
The value transmitted is the current torque in percent or per mil of the nominal actuator
torque.
The value is transmitted in per mil (value: 0 – 1,000).
●
The value 1,000 corresponds to 127.0 % torque in direction OPEN.
●
The value 500 is the torque zero point.
●
The value 0 corresponds to 127.0 % torque in direction CLOSE.
Byte 13: Not ready REMOTE 1
Table 10: Byte 13: Not ready REMOTE 1
Description
Value
Prm-Text-Def GSD file
Designation
(process representation)
Bit
Wrong operation command
Indicates the fact that several operation commands were
received simultaneously via Profibus DP (e.g. Remote
OPEN and Remote CLOSE simultaneously or Remote
CLOSE/Remote OPEN and Remote SETPOINT simultan-
eously) or that the max. value for a setpoint position has
been exceeded (setpoint position > 1,000).
1
(98) = "Bit: Wrong opera-
tion cmd"
Wrong oper. cmd
0
Operation commands are ok.
0
Selector switch is in position Local control (LOCAL) or
0 (OFF).
1
(53) = "Bit: Sel. sw. not
REMOTE""
Sel. sw. not REMOTE
1
Selector switch is in position Remote control (REMOTE).
0
Actuator is interlocked.
1
(52) = "Bit: Interlock active"
Interlock active
2
No signal
0
Push button STOP of local controls is operated.
1
(97) = "Bit: Local Stop"
Local STOP
3
No signal
0
Operation mode EMERGENCY stop is active (EMER-
GENCY stop button has been pressed).
1
(50) = "Bit: EMCY stop
active"
EMCY stop active
4
EMERGENCY stop button not pressed (normal operation).
0
Operation mode EMERGENCY behaviour is active
(EMERGENCY signal was sent).
1
(49) = "Bit: EMCY be-
hav.act."
EMCY behav. active
5
No signal
0
No valid communication via fieldbus (despite available
connection)
1
(47) = "Bit: FailState field-
bus"
FailState fieldbus
6
Communication via fieldbus is ok.
0
The actuator is controlled via the I/O interface (parallel).
1
(48) = "Bit: I/O interface"
I/O interface
7
The actuator is controlled via fieldbus.
0
27
Actuator controls
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Description of the data interface
Summary of Contents for AC(V) 01.2
Page 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Page 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Page 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Page 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...