Description
Designation
(process representation)
Prm-Text-Def GSD file
Collective signal 03:
Contains the result of a disjunction (OR operation) of all faults.
The actuator cannot be operated.
Fault
(20) = "Bit: Fault"
Collective signal 02:
Contains the result of an OR disjunction of all warnings.
Warning
(21) = "Bit: Warnings"
Collective signal 04:
Contains the result of a disjunction (OR-operation) of the signals,
forming the "Not ready REMOTE" group.
The actuator cannot be operated from REMOTE.
Not ready REMOTE
(22) = "Bit: Not ready REMOTE"
The actuator is in off-time (e.g. stepping mode or reversing preven-
tion time).
Operation pause active
(23) = "Bit: Op. pause active"
The actuator is within the set stepping range.
Start stepping mode
(24) = "Bit: Start step mode"
Actuator is running (output drive is moving)
Hard wired collective signal consisting of signals:
●
(26)
Running LOCAL
●
(27)
Running REMOTE
●
(28)
Handwheel oper.
Actuator running
(25) = "Bit: Actuator running"
Output drive rotates due to operation command from LOCAL.
Running LOCAL
(26) = "Bit: Running LOCAL"
Output drive rotates due to operation command from REMOTE.
Running REMOTE
(27) = "Bit: Running REMOTE"
Output drive rotates without electric operation command (manual
operation).
Handwheel oper.
(28) = "Bit: Running via handw."
The actuator is in an intermediate position e.g. neither in end posi-
tion OPEN nor in end position CLOSED.
In intermediate pos.
(29) = "Bit: In interm. position"
The failure behaviour is active.
Failure behav. active
(30) = "Bit: Failure behav. active"
Intermediate position 1 reached
Intermediate pos. 1
(31) = "Bit: Intermediate pos. 1"
Intermediate position 2 reached
Intermediate pos. 2
(32) = "Bit: Intermediate pos. 2"
Intermediate position 3 reached
Intermediate pos. 3
(33) = "Bit: Intermediate pos. 3"
Intermediate position 4 reached
Intermediate pos. 4
(34) = "Bit: Intermediate pos. 4"
Intermediate position 5 reached
Intermediate pos. 5
(35) = "Bit: Intermediate pos. 5"
Intermediate position 6 reached
Intermediate pos. 6
(36) = "Bit: Intermediate pos. 6"
Intermediate position 7 reached
Intermediate pos. 7
(37) = "Bit: Intermediate pos. 7"
Intermediate position 8 reached
Intermediate pos. 8
(38) = "Bit: Intermediate pos. 8"
A high signal (+24 V DC) is present at digital input 1.
Input DIN 1
(39) = "Bit: Input DIN 1"
A high signal (+24 V DC) is present at digital input 2.
Input DIN 2
(40) = "Bit: Input DIN 2"
A high signal (+24 V DC) is present at digital input 3.
Input DIN 3
(41) = "Bit: Input DIN 3"
A high signal (+24 V DC) is present at digital input 4.
Input DIN 4
(42) = "Bit: Input DIN 4"
A high signal (+24 V DC) is present at digital input 5.
Input DIN 5
(43) = "Bit: Input DIN 5"
A high signal (+24 V DC) is present at digital input 6.
Input DIN 6
(44) = "Bit: Input DIN 6"
Parameter not available
Input DIN 7
(45) = "Bit: Input DIN 7"
Parameter not available
Input DIN 8
(46) = "Bit: Input DIN 8"
No valid communication via fieldbus (despite available connection)
FailState fieldbus
(47) = "Bit: FailState fieldbus"
The actuator is controlled via the I/O interface (parallel).
I/O interface
(48) = "Bit: I/O interface"
Operation mode EMERGENCY is active (EMERGENCY signal was
sent).
EMCY behav. active
(49) = "Bit: EMCY behav.act."
Operation mode EMERGENCY stop is active (EMERGENCY stop
button pressed).
EMCY stop active
(50) = "Bit: EMCY stop active"
Operation mode Service (via Bluetooth) is active.
Service active
(51) = "Bit: Service active"
Actuator is interlocked.
Interlock active
(52) = "Bit: Interlock active"
Selector switch is in position Local control (LOCAL) or 0 (OFF).
Sel. sw. not REMOTE
(53) = "Bit: Sel. sw. not REMOTE"
Manual operation is active (handwheel is engaged); optional signal
Handwheel active
(54) = "Bit: Handwheel active"
14
Actuator controls
Commissioning
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Summary of Contents for AC(V) 01.2
Page 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Page 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Page 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Page 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...