Description
Value
Prm-Text-Def GSD file
Designation
(process representation)
Bit
Partial Valve Stroke Test (PVST) was aborted or could
not be started. Remedy: Perform RESET or restart PVST.
1
(118) = "Bit: PVST abort"
PVST abort
6
No signal
0
Partial Valve Stroke Test (PVST) could not be successfully
completed.
1
(117) = "Bit: PVST fault"
PVST fault
7
No signal
0
Byte 21 and byte 22: Input AIN 2
Byte 21 = high byte, byte 22 = low byte.
Bytes 9 and 10 transmit the value of the second additional free analogue current
input of the Profibus DP interface. The start and end values can be set at the AC via
push buttons and display. (For operation, please refer to the respective operation
instructions for the actuator.)
If the measuring values are 0.3 mA below the initial value, a signal loss is indicated.
The value is transmitted in per mil (value: 0 – 1,000).
Byte 23: Failure
Causes of the Failure signal in accordance with NAMUR recommendation NE 107.
Table 18: Byte 23: Failure
Description
Value
Prm-Text-Def GSD file
Designation
(process representation)
Bit
No signal (reserved)
—
—
0
No signal (reserved)
—
—
1
No signal (reserved)
—
—
2
No signal (reserved)
—
—
3
No signal (reserved)
—
—
4
No signal (reserved)
—
—
5
No signal (reserved)
—
—
6
Collective signal 03:
Contains the result of a disjunction (OR-operation) of all
bits of bytes 15 and 16 (Fault 1 and Fault 2).
The actuator cannot be operated.
1
(20) = "Bit: Fault"
Fault
7
In bytes 15 and 16, no faults are active (all bits are set to
0).
0
Byte 24: Maintenance required
Causes of the Maintenance required signal in accordance with NAMUR
recommendation NE 107.
Table 19: Byte 24: Maintenance required
Description
Value
Prm-Text-Def GSD file
Designation
(process representation)
Bit
Mechanic maintenance requirement (AUMA service)
1
(209) = "Mechanic lifetime"
Mainten. mechanics
0
No signal
0
Seal maintenance requirement (AUMA service)
1
(210) = "Seal lifetime"
Mainten. seals
1
No signal
0
Lubricant maintenance requirement (AUMA service)
1
(211) = "Seal lifetime"
Mainten. lubricant
2
No signal
0
Contactor maintenance requirement (AUMA service)
1
(212) = "Contactor lifetime"
Mainten. contactors
3
No signal
0
The set maintenance interval has expired.
1
(213) = "Maintenance inter-
val"
Mainten. interval
4
No signal
0
31
Actuator controls
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Description of the data interface
Summary of Contents for AC(V) 01.2
Page 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Page 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Page 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Page 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...