10
Technical specification
Power supply
• Voltage Vcc
• Power
230 V ~ ± 10%
10 W
Environment
In operation
Storage
• Ambient temperatures
• Humidity
0 – 40
O
C
10 – 90 % long term
0 – 99 % short term
0 – 40
O
C
30 – 90 % long term
IP
IP 65
Analogue input parameters
• R
IN
• U
z
• I
z
200 Ω
10.5 – 14 V
160 mA
Number of analogue inputs
1 – 2
Parameters of the input for an
external alarm signal
Potential-free contact
Below 10 Ω inactive
Above 5000 Ω active
Minimum duration of the switchover pulse > 1s
Digital output parameters
• Relay R1 – R3
• Voltage outputs OC1, OC2
Not protected
230 V ~ / 1 A
230 V / 0.25 A
24 V / 1 A
Voltage 14 V
Σ I < 300 mA
*
Valve control outputs
PW-054-P17-XEF-
1212
PW-054-P17-XEF-1240
PW-054-P17-
230V
• Valve type
• Guaranteed limit of the shutoff voltage
• Min. Value of the load resistance
• Maximum resistance of the power supply
line
• The type of shutoff signal
Poppet
10.5 – 13.8 V
4 Ω
0.5 Ω
3 x 0.5 s
Poppet
10.5 – 13.8 V
4 Ω
0.5 Ω
3 x 0.5 s
Ball, flap
10.5 – 13.8 V
0,5 Ω
0.2 Ω
3 x 0.5 s
Poppet
230VAC
-
-
3 x 0.5 s
Integrated signalling equipment
(visual)
LED controls
Integrated signalling equipment
(audible)
60 dB, 1 m distance
Protection class
II
Required protections
• Power supply
Overcurrent fuse switch C2 in L and N lines
Duration of operation with backup voltage
• PW-054-LED2-1212
• PW-054-P17-XEF-1240
1h
1h
Dimension
See Figure 1
*
The total current consumed by devices connected to the control unit (through gas detector and signaling device terminals) may not exceed 500
mA, while the current consumed by the signalling device terminals may not exceed 300 mA.