Lifetime cycle
9.1
Transportation
The device can be shipped in the same way as new equipment of that type. If the original package or
another protecting means (e.g. corks) is unavailable the conveyed equipment must be secured against
shocks, vibrations or moisture by means of adequate methods and material at the own responsibility of the
sender.
Ambient conditions for transportations are specified in Table 18.
9.2
Installation
The module must be mounted in a flat, vertical wall with cable glands downwards, where the mounting
position is shown in Figure 1. It is recommended to mount the device at the elevation that enables easy
handling of the unit.
If multi-core strands (commonly referred to as "cables") are used for connection, the ends of these strands
shall be provided with terminal ferrules and lugs.
When two or more conductors are to be connected to a single terminal of the device all these conductors
must be clamped beforehand into a common ferrule with a lug (see details in Table 18).
It is not allowed to combine two or mode conductors with individual ferrules and lugs in a
single terminal.
It is not allowed to leave spare lengths of cables inside the device. Bare wires or wires
surplus may lead to a hazard of electric shock or equipment damage.
All cable cores must be terminated inside the device. Leaving of unterminated cores is not
allowed.
Incorrect routing of cables may lead to compromising the device immunity to
electromagnetic interferences.
Not used screw terminals must be tightly screwed.