![ASI Tiger TG-1000 Instruction Manual Download Page 39](http://html1.mh-extra.com/html/asi/tiger-tg-1000/tiger-tg-1000_instruction-manual_2982756039.webp)
11
CCA Z=
Description
Display Comment
23
Joystick polarity of card's first axis set to default
l
Firmware
Default,V3.05 and
later
24
Reverses joystick polarity of the card's second axis
r
V3.05 and later
25
Joystick polarity of card's first axis set to default
l
Firmware
Default,V3.05 and
later
Note: A few products have different axis names. When in doubt, call ASI.
Format:
[
Addr#]CCA Z?
Function:
Transmits string of sign characters for all active axes, then clutch and display status
characters.
Note 1:
When the direction of an axis is negative, upper limit settings must be negative
values, and lower limit settings must be positive values.
Command: CUSTOMB (PLANAR_CORRECTION firmware module required)
Shortcut:
CCB
Format:
[Addr#]CCB Z=n
Function:
Planar correction functions. It’s a
Card-Addressed command.
1CCB Z=1
1CCB Z=2
1CCB Z=3
Store current xyz location values x1,y1,z1…x3,y3,z3 respectively.
1CCB Z=4
Calculate coefficients for planar correction function, and enable planar
correction
1CCB Z=5
Disable planar correction.
1CCB Z=6
Displays actual corrected current Z position as long integer.
Note:
WHERE Z
displays the intended position of Z based on the most recently sent
MOVE, MOVEREL
, or
HERE
command.
1CCB Z=7
Re-initialize to zero all Planar variables including x1,y1,z1…x3,y3,z3 and
planar correction function coefficients. Disable planar correction.
Summary of Contents for Tiger TG-1000