Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0
PAG. 39
no. Param.
Description
Dec.
Point
Values
Default
128 oPr.E
Operative modes ena-
bling
ALL =
All modes will be selectable by the next parameter
Au.oP = Auto and manual (OPLO) mode only will be selectable by the next
parameter
Au.Sb = Auto and Stand-by modes only will be selectable by the next parameter
ALL
129 oPEr
Operative mode selection
If oPr.E = ALL:
- Auto = Auto mode
-
oPLo = Manual mode
-
St.bY = Stand by mode
If oPr.E = Au.oP: -
Auto = Auto mode
- oPLo = Manual mode
If oPr.E = Au.Sb:
- Auto = Auto mode
-
St.bY = Stand by mode
Auto
]
Ser group - Serial link parameters
no. Param.
Description
Dec.
Point
Values
Default
130 Add
Instrument address
- oFF
- 1... 254
1
131 bAud
baud rate
1200 = 1200 baud
2400 = 2400 baud
9600 = 9600 baud
19.2 = 19200 baud
38.4 = 38400 baud
9600
132 trSP
Selection of the value to be
retransmitted (Master)
nonE = Retransmission not used (the instrument is a slave)
rSP =
The instrument becomes a Master and retransmits the
operative set point
PErc = The instrument become a Master and it retransmits the
power output
nonE
]
COn group - Consumption parameters
no. Param.
Description
Dec.
Point
Values
Default
133 Co.tY
Measurement type
oFF =
Not used
1 =
Instantaneous power (kW)
2 =
Power consumption (kW/h)
3 =
Energy used during program execution. This measure starts
from zero when a program runs end stops at the end of the
program. A new program execution will reset the value
4 =
Total worked days with threshold. It is the number of hours
that the instrument is turned ON divided for 24
5 =
Total worked hours with threshold. It is the number of hours
that the instrument is turned ON
oFF
134 UoLt
Nominal Voltage of the load
1... 9999 (V)
230
135 cur
Nominal current of the load
1... 999 (A)
10
136 h.Job
Threshold of the working period
oFF =
threshold not used
0... 9999 days (when [133] cotY = 4)
0... 9999 hours (when [133] cotY = 5)
0
137 t.Job
Worked time (not resettable)
0... 9999 days
]
CAl group - user calibration parameters
no. Param.
Description
Dec.
Point
Values
Default
138 AL.P
Adjust Low Point
From -1999 to (AH.P - 10) in engineering units
0
139 AL.o
Adjust Low Offset
-300... +300 (E.U.)
0
140 AH.P
Adjust High Point
From (AL.P + 10) to 9999 engineering units
9999
141 AH.o
Adjust High Offset
-300... +300
0