[97] Pr.G1 - Gradient of the first ramp
Available:
When [92] Pr.F is different from nonE or [92] Pr.F
is different from S.uP.d.
Range:
0.1... 999.9 engineering units per minute;
inF =
Step transfer.
[98] Pr.t1 - Time of the first soak
Available:
When [92] Pr.F is different from nonE
Range:
0.00... 99.59 Time units.
[99] Pr.b1 - Wait band of the first soak
Available:
When [92] Pr.F is different from nonE or [92] Pr.F
is different from S.uP.d.
Range:
OFF... 9999 engineering units
Note:
The wait band suspends the time counting when
the measured value goes out of the defined band
(guaranteed soak).
Temperature
Wait
Wait
Soak x
Soak x
Ramp x + 1
Ramp x
Wait
Soak SP
Wait
SP
Measur
e
[100] Pr.E1 - Events of the first group
Available:
When [92] Pr.F is different from nonE or [92] Pr.F
is different from S.UP.d.
Range:
00.00... 11.11 where:
0 =
event OFF;
1 =
event ON.
Event 1 status during ramp
Event 2 status during ramp
Event 1 status during soak
Event 2 status during soak
Display
Ramp
Soak
Event 1
Event 2
Event 1
Event 2
00.00
off
off
off
off
10.00
on
off
off
off
01.00
off
on
off
off
11.00
on
on
off
off
00.10
off
off
on
off
10.10
on
off
on
off
01.10
off
on
on
off
11.10
on
on
on
off
00.01
off
off
off
on
10.01
on
off
off
on
01.01
off
on
off
on
11.01
on
on
off
on
00.11
off
off
on
on
10.11
on
off
on
on
01.11
off
on
on
on
11.11
on
on
on
on
[101] Pr.S2 - Set point of the second soak
Available:
When [92] Pr.F is different from nonE
Range:
From [76] SPLL to [77] SPHL
oFF = Program end.
Note:
It is not necessary to configure all steps.
When you use for example 2 groups only, it is
sufficient to set the set point of the third group equal
to OFF. The instrument will mask all the following
parameters of the programmer.
[102] Pr.G2 - Gradient of the second ramp
Available:
When [92] Pr.F is different from nonE and [102]
Pr.S2 is different from oFF.
Range:
0.1... 999.9 engineering units per minute;
inF =
Step transfer.
[103] Pr.t2 - Time of the second soak
Available:
When [92] Pr.F is different from nonE and
[101] Pr.S2 is different from oFF.
Range:
0.00... 99.59 time units.
[104] Pr.b2 - Wait band of the second soak
Available:
When [92] Pr.F is different from nonE and
[101] Pr.S2 is different from oFF.
Range:
OFF... 9999 engineering units.
Note:
For more details see [99]Pr.b1 parameter.
[105] Pr.E2 - Events of the second group
Available:
When [92] Pr.F is different from nonE and
[101] Pr.S2 is different from oFF.
Range:
00.00... 11.11 where:
0 =
Event OFF;
01 =
Event ON.
Note:
For more details see [100]Pr.E1 parameter.
[106] Pr.S3 - Set point of the third soak
Available:
When [92] Pr.F is different from nonE and
[101] Pr.S2 is different from oFF
Range:
from [76] SPLL to [77] SPHL;
oFF = Program end.
Note:
For more details see [101]Pr.S2 parameter.
[107] Pr.G3 - Gradient of the third ramp
Available:
When [92] Pr.F is different from nonE, [101]
Pr.S2 is different from oFF and [106] Pr.S3 is
different from OFF.
Range:
0.1... 999.9 engineering units per minute;
inF =
Step transfer.
[108] Pr.t3 - Time of the third soak
Available:
When [92] Pr.F is different from nonE, [101]
Pr.S2 is different from oFF and [106] Pr.S3 is
different from OFF.
Range:
0.00... 99.59 time units.
[109] Pr.b3 - Wait band of the third soak
Available:
When [92] Pr.F is different from nonE, [101]
Pr.S2 is different from oFF and [106] Pr.S3 is
different from OFF.
Range:
OFF... 9999 engineering units.
Note:
For more details see [99]Pr.b1 parameter
[110] Pr.E3 - Events of the third group
Available:
When [92] Pr.F is different from nonE, [101]
Pr.S2 is different from oFF and [106] Pr.S3 is
different from OFF.