Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0
PAG. 37
no. Param.
Description
Dec.
Point
Values
Default
90
tr.t2
Time 2
2
When tr.u < 2: From 00.00 (oFF) to 99.59 (inF)
1.00
1
When tr.u = 2: From 000.0 (oFF) to 995.9 (inF)
91
tr.St
Timer status
0
rES =
Timer reset
run =
Timer run
HoLd = Timer hold
rES
]
PRG group - Programmer function parameters
no. Param.
Description
Dec.
Point
Values
Default
92
Pr.F
Program action at power up
0
nonE = Programmer not used
S.uP.d = Start at power up with a first step in stand-by
S.uP.S = Start at power up
u.diG = Start at Run command detection only
u.dG.d = Start at Run command with a first step in stand-by
nonE
93
Pr.u
Engineering unit of the soaks
2
hh.nn = Hours and minutes
nn.SS = Minutes and seconds
hh.nn
94
Pr.E
Instrument behaviour at the end of
the program execution
0
cnt =
continue
A.SP = go to the set point selected by A.SP
St.by = go to stand-by mode
A.SP
95
Pr.Et
Time of the end program indication
2
From 0.00 (oFF) to 99.59 (inF) minutes and seconds
oFF
96
Pr.S1
Set point of the first soak
dP
From SPLL to SPHL
0
97
Pr.G1
Gradient of the first ramp
1
0.1... 999.9 (inF= Step transfer) Engineering Unit/minute
inF
98
Pr.t1
Time of the 1
st
soak
2
0.00... 99.59
0.10
99
Pr.b1
Wait band of the 1
st
soak
dP
From 0 (oFF) to 9999 (E.U.)
oFF
100 Pr.E1
Events of the 1
st
group
2
00.00... 11.11
00.00
101 Pr.S2
Set point of the 2
nd
soak
dP
OFF or from SPLL to SPHL
0
102 Pr.G2
Gradient of the 2
nd
ramp
1
0.1... 999.9 (inF= Step transfer) Engineering Unit/minute
inF
103 Pr.t2
Time of the 2
nd
soak
2
0.00... 99.59
0.10
104 Pr.b2
Wait band of the 2
nd
soak
dP
From 0 (oFF) to 9999 (E.U.)
oFF
105 Pr.E2
Events of the 2
nd
group
2
00.00... 11.11
00.00
106 Pr.S3
Set point of the 3
rd
soak
dP
OFF or from SPLL to SPHL
0
107 Pr.G3
Gradient of the 3
rd
ramp
1
0.1... 999.9 (inF= Step transfer) Engineering Unit/minute
inF
108 Pr.t3
Time of the 3
rd
soak
2
0.00... 99.59
0.10
109 Pr.b3
Wait band of the 3
rd
soak
dP
From 0 (oFF) to 9999 (E.U.)
oFF
110 Pr.E3
Events of the 3
rd
group
0
00.00... 11.11
00.00
111 Pr.S4
Set point of the 4
th
soak
dP
OFF or from SPLL to SPHL
0
112 Pr.G4
Gradient of the 4
th
ramp
1
0.1... 999.9 (inF= Step transfer) Engineering Unit/minute
inF
113 Pr.t4
Time of the 4
th
soak
2
0.00... 99.59
0.10
114 Pr.b4
Wait band of the 4
th
soak
dP
From 0 (oFF) to 9999 (E.U.)
oFF
115 Pr.E4
Events of the 4
th
group
0
00.00... 11.11
00.00
116 Pr.St
Program status
0
rES =
Program reset
run =
Program start
HoLd = Program hold
rES
]
PAn group - Operator hMI parameters
no. Param.
Description
Dec.
Point
Values
Default
117 PAS2
Level 2 password (limited
access level)
0
- oFF (Level 2 not protected by password)
- 1... 200
20
118 PAS3
Level 3 password (com-
plete configuration level) 0
3... 200
30
119 PAS4
Level 4 password (CODE
configuration level)
0
201... 400
300