Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0
PAG. 36
no. Param.
Description
Dec.
Point
Values
Default
58
SELF
Self tuning enabling
0
no =
The instrument does not perform the self-tuning
YES = The instrument is performing the self-tuning
no
59
HSEt
Hysteresis of the ON/OFF control
dP
0... 9999 (E.U.)
1
60
cPdt
Time for compressor protection
0
From 0 (oFF) to 9999 (s)
oFF
61
Pb
Proportional band
dP
1... 9999 (E.U.)
50
62
ti
Integral time
0
From 0 (oFF) to 9999 (s)
200
63
td
Derivative time
0
From 0 (oFF) to 9999 (s)
50
64
Fuoc
Fuzzy overshoot control
2
0.00... 2.00
0.50
65
tcH
Heating output cycle time
1
0.1... 130.0 (s)
20.0
66
rcG
Power ratio between heating and
cooling action
2
0.01... 99.99
1.00
67
tcc
Cooling output cycle time
1
0.1... 130.0 (s)
20.0
68
rS
Manual reset (Integral pre-load)
1
-100.0... +100.0 (%)
0.0
69
Str.t
Servomotor stroke time
0
5...1000 seconds
60
70
db.S
Servomotor dead band
0
0...100%
50
71
od
Delay at power up
2
From 0.00 (oFF) to 99.59 (hh.mm)
oFF
72
St.P
Maximum power output used during
soft start
0
-100... 100 (%)
0
73
SSt
Soft start time
2
- 0.00 (oFF)
- 0.01... 7.59 (hh.mm)
- inF (always ON)
oFF
74
SS.tH
Threshold for soft start disabling
dP
-1999... +9999 (E.U.)
9999
]
SP group - Set point parameters
no. Param.
Description
Dec.
Point
Values
Default
75
nSP
Number of used set points
0
1... 4
1
76
SPLL
Minimum set point value
dP
From -1999 to SPHL
-1999
77
SPHL
Maximum set point value
dP
From SPLL to 9999
9999
78
SP
Set point 1
dP
From SPLL to SPLH
0
79
SP 2
Set point 2
dP
From SPLL to SPLH
0
80
SP 3
Set point 3
dP
From SPLL to SPLH
0
81
SP 4
Set point 4
dP
From SPLL to SPLH
0
82
A.SP
Selection of the active set point
0
From 1 (SP 1) to nSP
1
83
SP.rt
Remote set point type
0
RSP = The value coming from serial link is used as remote
set point
trin =
The value will be added to the local set point selected
by A.SP and the sum becomes the operative set point
PErc = The value will be scaled on the input range and this
value will be used as remote SP
trin
84
SPLr
Local/remote set point selection
0
Loc =
local
rEn = remote
Loc
85
SP.u
Rate of rise for
POSITIVE
set point
change (ramp UP)
2
0.01... 99.99 (inF) Eng. units per minute
inF
86
SP.d
Rate of rise for
NEGATIVE
set point
change (ramp DOWN)
2
0.01... 99.99 (inF) Eng. units per minute
inF
]
TIN group - Timer function parameters
no. Param.
Description
Dec.
Point
Values
Default
87
tr.F
Independent timer function
0
NonE = Timer not used
i.d.A = Delayed start timer
i.uP.d = Delayed start at power up
i.d.d = Feed-through timer
i.P.L = Asymmetrical oscillator with start OFF
i.L.P = Asymmetrical oscillator with start ON
nonE
88
tr.u
Timer unit
0
hh.nn = Hours and minutes
nn.SS = Minutes and seconds
SSS.d = Second and tenth of seconds
nn.SS
89
tr.t1
Time 1
2
When tr.u < 20: 0.01... 99.59
1.00
1
When tr.u = 200: 0.1... 995.9