Domestic Ventilation with Heat Recovery
KNX-LUNOS-CONTROL4
Subject to change
Arcus-EDS GmbH
www.arcus-eds.de
Rigaer Str. 88 10247 Berlin
[email protected]
Tel.: +49(0)30 25933914
Fax.: +49(0)30 25933915
682x-Lunos-Control-4F
V.13.09.2022
e1
8. ) HVAC mode 3 ( Object-5 ) *
9. ) HVAC night mode ( Object-2 ) *
10. ) HVAC manual mode ( Object-1 ) *
11. ) HVAC automatic mode ( Object-0 )
12. ) if Object 0 == 0 then Standard HVAC Mode as set in Settings 3.2
If in Stages mode:
1. ) System lock ( Object-25 )
2. ) Supply air/exhaust air request ( Object-21 ) if supply/exhaust air request is active
3. ) Slave operation ( Object-26 ) wenn im Slave-Betrieb
4. ) Fan stage manual operation ( Object-7 ) *
5. ) Fan stage calculated from leads and set stage
6. ) Stage mode 1 ( Object-3 ) *
7. ) Stage mode 2 ( Object-4 ) *
8. ) Stage mode 3 ( Object-5 ) *
9. ) Stage night mode ( Object-2 ) *
10. ) Stage manual mode ( Object-1 ) *
11. ) Stage automatic mode ( Object-0 )
12. ) if Object 0 == 0 then Standard Stage as set in Settings 3.4
In the event of changes in the objects marked with *, the objects are reset with higher priority in order
to get a reaction of the system, except for conditions 1) -3) that always have priority.
Control examples:
With the following operating order:
HVAC-Automatic -> HVAC-Night-mode -> HVAC-Operation-mode-1
initially HVAC operation mode 1 is active, after reset (or timeout) the HVAC night operation is active
again.
In this order
HVAC-Automatic -> HVAC-Operation-mode-1 -> HVAC-Night-mode
The night operation deletes operating type1, after resetting the night operation, the control goes into
the HVAC automatic operation.
Master-slave-operation:
A control unit that works in master operation mode can control several devices in slave operation
mode.The direction and level information is placed via the object-26 IO-Master/slave. If the fan A runs
in the master device in air-supply mode, A also runs in the slave device in the air-supply. If only one fan
is connected, one device must be operated on connection A and one at the connection B.It is always to
be ensured the balance between supply air and exhaust air devices (same number A and B slots),
otherwise the required air exchange and the desired heat recovery will not be reached.
Filter cleaning alert:
Depending on the speed of the fan, cleaning or changing the fan filter is regularly necessary. After