Domestic Ventilation with Heat Recovery
KNX-LUNOS-CONTROL4
Subject to change
Arcus-EDS GmbH
www.arcus-eds.de
Rigaer Str. 88 10247 Berlin
[email protected]
Tel.: +49(0)30 25933914
Fax.: +49(0)30 25933915
682x-Lunos-Control-4F
V.13.09.2022
e1
Functional block lead temperature - KNX-objects
IO
Name
Function
Datapoint type
10
Input
Indoor temperature
Input for interior
temperature
measurement of
another KNX device
DPT 9.001
11
Input
Outdoor
temperature
Input for outside
temperature
measurement of
another KNX device
DPT 9.001
12
Input
Temperature
setpoint
Input for
temperature setpoint
value from another
KNX device, usually
connected to the
setpoint of the
heating factor.
DPT 9.001
13
Input
Lead temperature
enable
The lead calculation
of the fan level
through the
temperatures can be
deactivated with a
"0".
DPT 1.003