Domestic Ventilation with Heat Recovery
KNX-LUNOS-CONTROL4
Subject to change
Arcus-EDS GmbH
www.arcus-eds.de
Rigaer Str. 88 10247 Berlin
[email protected]
Tel.: +49(0)30 25933914
Fax.: +49(0)30 25933915
682x-Lunos-Control-4F
V.13.09.2022
e1
Functional block lead CO2 - KNX-Objects
IO
Name
Function
Datapoint type
17
Input
CO2 (Air quality)
Input for CO2 (air
quality) from another
KNX device
DPT 9.008
18
Input
Lead CO2 enable
The lead calculation
of the fan level
through the CO2
concentration can be
deactivated with a
"0".
DPT 1.003
3.13 Limit values for fan levels in CO2 and humidity lead calculation
The 3 fan levels are switched over 4 limit values.Fan level 1 is only activated when the limit value 2 is
reached, but the limit value 1 has to be fallen below again.The same applies accordingly to the higher
fan levels.If this or a higher fan level is already active, exceeding a limit has no effect.
3.14 Priorities of the used objects
The objects that influence the fan control have a order in which they are weighted. If in HVAC mode:
1. ) System lock ( Object-25 )
2. ) Supply air/exhaust air request ( Object-21 ) if supply/exhaust air request is active
3. ) Slave operation ( Object-26 ) wenn im Slave-Betrieb
4. ) HVAC mode manual operation ( Object-7 ) *
5. ) HVAC mode calculated from leads and set HVAC modes
6. ) HVAC mode 1 ( Object-3 ) *
7. ) HVAC mode 2 ( Object-4 ) *