Domestic Ventilation with Heat Recovery
KNX-LUNOS-CONTROL4
Subject to change
Arcus-EDS GmbH
www.arcus-eds.de
Rigaer Str. 88 10247 Berlin
[email protected]
Tel.: +49(0)30 25933914
Fax.: +49(0)30 25933915
682x-Lunos-Control-4F
V.13.09.2022
e1
Obj
IO
Name
Function
Datapoint type
22
Input
Supply request
Switching output to
set external fans into
the supply air
operation
DPT 1.001
25
Input
System lock
Blocks all fans and
functions
DPT 1.001
28
Output
Filter change
One of the fan pairs
has reached the
maximum time
without a filter change
*)
DPT 1.005
29
Input
Filter change
acknowledge
After
changing/cleaning the
filter, this must be
acknowledged here *)
DPT 1.016
30
Input/Output
Time control
Runtime control **)
DPT 7.000
*) Object 28 can be reset for a short time via the object itself or in the
long term via object 29.
**) Every action associated with a timeout writes its timeout on this
object. Writing to this object leads to the change of the timeout parameter
of this action. The timeout must be changed within 60 seconds. If this time
has expired the desired operating mode must be selected again.