Domestic Ventilation with Heat Recovery
KNX-LUNOS-CONTROL4
Subject to change
Arcus-EDS GmbH
www.arcus-eds.de
Rigaer Str. 88 10247 Berlin
[email protected]
Tel.: +49(0)30 25933914
Fax.: +49(0)30 25933915
682x-Lunos-Control-4F
V.13.09.2022
e1
Night
Intense ventilation
Exhaust request
This function is carried out in response to a short key press.
Default: Step +/-
Timeout [min]
0 .. 240
Duration for short function, after that the selected function is deactivated
Long function
without function
Step +/-
Off
Night
Intense ventilation
Exhaust request
This function is carried out in response to a long key press.
Default: Normal operation/Fan off
Timeout [min]
0 .. 240
Duration for long function, after that the selected function is deactivated
Double function
without function
Step +/-
Off
Night
Intense ventilation
Exhaust request
This function is carried out in response to a double key press.
Default: Intense ventilation/Normal mode
Timeout [min]
0 .. 240
Duration for double press function, after that the selected function is deactivated
Debounce time [ms]
2 .. 100
Depending on the button used, longer debounce times may be necessary if double