Domestic Ventilation with Heat Recovery
KNX-LUNOS-CONTROL4
Subject to change
Arcus-EDS GmbH
www.arcus-eds.de
Rigaer Str. 88 10247 Berlin
[email protected]
Tel.: +49(0)30 25933914
Fax.: +49(0)30 25933915
682x-Lunos-Control-4F
V.13.09.2022
e1
actuations are mistakenly displayed
Functional block potential free contacts ( Push buttons ) - KNX-Objects
Obj
IO
Name
Function
Datapoint type
23
Output
Short function
Switching output
0/1 if the button
inputs are pressed
short
DPT 1.001
24
Output
Long function
Switching output
0/1 if the button
inputs are pressed
long
DPT 1.001
Functional block potential free contacts ( Switches ) - Parameters
Switch settings
With switch 1 is chosen between manual and automatic mode. In manual mode, the fan stages are
selected via switch 2 as follows.
Function switch 2 [OFF]
Off
Fan stage 1
Fan stage 2
Fan stage 3
In the case of switch position [off], the set fan level is switched on.
Function switch 2 [ON]
Off
Fan stage 1
Fan stage 2
Fan stage 3
In the case of switch position [on], the set fan level is switched on.
Debouncing time [ms]
2 .. 100
Depending on the switch used, longer debounce times may be necessary if double
actuations are mistakenly displayed.