Instruction manual
–
AQ F3x0 Feeder protection IED
56 (162
)
3.2.7
C
URRENT UNBALANCE
(60)
The current unbalance protection function can be applied to detect unexpected asymmetry in
current measurement.
The applied method selects maximum and minimum phase currents (fundamental Fourier
components). If the difference between them is above the setting limit, the function generates
a start signal.
Structure of the current unbalance protection function is presented in the figure below
Figure 3-32: Structure of the current unbalance protection algorithm.
The analogue signal processing principal scheme is presented in the figure below.
Figure 3-33: Analogue signal processing for the current unbalance function.