Residual directional overcurrent protection function I0Dir>, I0Dir>>
(67N)
Pick-up current inaccuracy
< 2%
Operation time inaccuracy
±5% or ±
15ms
Reset ratio
0.95
Minimum operating time with IDMT
35ms
Reset time
Approx 35ms
Transient overreach
2 %
Pickup time
25
–
30ms
Angular inaccuracy
<3°
7.1.3
V
OLTAGE PROTECTION FUNCTIONS
Overvoltage protection function U>, U>> (59)
Pick-up starting inaccuracy
< 0,5 %
Reset time
U>
→
Un
U>
→ 0
50 ms
40 ms
Operation time inaccuracy
+ 15 ms
Undervoltage protection function U<, U<< (27)
Pick-up starting inaccuracy
< 0,5 %
Reset time
U>
→
Un
U>
→ 0
50 ms
40 ms
Operation time inaccuracy
+ 15 ms
Residual overvoltage protection function U0>, U0>> (59N)
Pick-up starting inaccuracy
< 0,5 %
Reset time
U>
→
Un
U>
→ 0
50 ms
40 ms
Operate time inaccuracy
+ 15 ms