Instruction manual
–
AQ F3x0 Feeder protection IED
132 (162
)
3.3.15
LED
ASSIGNMENT
On the front panel of the device there is “User LED”
-
s with the “Changeable LED description
label”
. Some LED-s are factory assigned, some are free to be defined by the user. Table
below shows the LED assignment of the AQ-F350 factory configuration.
Table 3-71 The LED assignment
LED
Explanation
Gen. Trip
Trip command generated by the TRC94 function
OC trip
Trip command generated by the phase overcurrent protection functions
OCN trip
Trip command generated by the residual overcurrent protection functions
Therm. Trip
Trip command of the line thermal protection function
Unbal. Trip
Trip command of the current unbalance protection function
Inrush
Inrush current detected
Voltage trip
Trip command generated by the voltage-related functions
Frequ trip
Trip command generated by the frequency-related functions
REC blocked
Blocked state of the automatic reclosing function
Reclose
Reclose command of the automatic reclosing function
Final trip
Final trip command at the end of the automatic reclosing cycles
LED 312
Free LED
LED 313
Free LED
LED 314
Free LED
LED 315
Free LED
LED 316
Free LED