Instruction manual
–
AQ F3x0 Feeder protection IED
59 (162
)
Table 3-22: Setting parameters of the current unbalance function
Parameter
Setting value, range
and step
Description
Operation
On
Off
Selection for the function enabled or disabled. Default setting
is “On” which means function is enabled.
Start signal
only
Activated
Deactivated
Selection if the function issues either “Start” signal alone or
both “Start” and after set time delay “Trip” signal.
Default is
that both signals are generated (=deactivated).
Start current
10…90 % by step of
1 %
Pick up setting of the current unbalance. Setting is the
maximum allowed difference in between of the min and max
phase currents. Default setting is 50 %.
Time delay
0…60000 ms by step
of 100 ms
Operating time delay setting for the “Trip” signal from the
“Start” signal.
Default setting is 1000 ms.