AQ F3x0 Feeder protection IED
141 (162
)
6.3
B
INARY INPUT MODULE
(DI12)
The inputs are galvanic isolated and the module converts high-voltage signals to the voltage
level and format of the internal circuits. This module is also used as an external IRIG-B
synchronization input. Dedicated synchronization input (input channel 1) is used for this
purpose.
The binary input modules are
•
Rated input voltage: 110/220Vdc
•
Clamp voltage: falling 0.75Un, rising 0.78Un
•
Digitally filtered per channel
•
Current drain approx.: 2 mA per channel
•
12 inputs.
•
IRIG-B timing and synchronization input
No. Name
1 BIn_F01
2 BIn_F02
3 BIn_F03
4 Opto-(1-3)
5 BIn_F04
6 BIn_F05
7 BIn_F06
8 Opto-(4-6)
9 BIn_F07
10 BIn_F08
11 BIn_F09
12 Opto-(7-9)
13 BIn_F10
14 BIn_F11
15 BIn_F12
16 Opto-(10-12)
"F" O12+/1101