Instruction manual
–
AQ F3x0 Feeder protection IED
107 (162
)
U_bus
VTS
U_bus
100
m
s
1000ms
Blk
OR
Calc
UlineFour (3ph)
-fi_ diff
-U_bus
-U_line
Ubus1Four
Ubus2Four
BusSel
VTS Blk
Bus1 VTS Blk
Bus2 VTS Blk
-U_diff
-f_diff
Parameters
SYN25_Com
Figure 3-58: Synchrocheck common difference calculation function structure.
If the active bus section changes the function is dynamically blocked for 1000ms and no
release signal or switching command is generated. The processed line voltage is selected
based on the preset parameter (Voltage select). The choice is: L1-N, L2-N, L3-N, L1-L2,
L2-L3 or L3-L1. The parameter value must match the input voltages received from the bus
sections. The active bus section is selected by the input signal (Bus select). If this signal is
logic TRUE, then the voltage of Bus2 is selected for evaluation.
The software block SYN25_Eva is applied separately for automatic and manual commands.
This separation allows the application to use different parameter values for the two modes
of operation.
The structure of the evaluation software block is shown in the following figure.