Instruction manual
–
AQ F3x0 Feeder protection IED
155 (162
)
Breaker failure protection function CBFP, (50BF)
Current inaccuracy
<2 %
Re-trip time
Approx. 15ms
Operation time inaccuracy
+ 5ms
Current reset time
20ms
Inrush current detection function INR2, (68)
Current inaccuracy
<2 %
Reset ratio
0,95
Operating time
Approx. 20 ms
Distance protection Z> (21)
Number of zones
5
Current effective range
20
…
2000% of In
Voltage effective range
2
…
110% of Un
Operation inaccuracy (current & voltage)
±
1%
Impedance effective range
0.1
–
200 Ohm (In =1A)
0.1
–
40 Ohm (In = 5A)
Impedance operation inaccuracy
±
5%
Zone static range
48
…
52Hz
49.5
…
50.5Hz
Zone static inaccuracy
±
5% (48..52Hz)
±
2% (49.5
…
50.5Hz)
Zone angular inaccuracy
±
3
°
Minimum operate time
<20ms
Typical operate time
25ms
Operate time inaccuracy
±
3ms
Reset time
16-25ms
Reset ratio
1.1
7.2
M
ONITORING FUNCTIONS
Voltage transformer supervision function VTS, (60)
Pick-up voltage inaccuracy
1%
Operation time inaccuracy
<20ms
Reset ratio
0.95