Instruction manual
–
AQ F3x0 Feeder protection IED
110 (162
)
Binary status signal
Title
Explanation
SYN25_BusSel_GrO_
Bus select
If this signal is logic TRUE, then the
voltage of Bus2 is selected for
evaluation
SYN25_VTSBlk_GrO_
VTS Block
Blocking signal of the voltage
transformer
supervision
function
evaluating the line voltage
SYN25_Bus1VTSBlk_GrO_
VTS Bus1 Block
Blocking signal of the voltage
transformer
supervision
function
evaluating the Bus1 voltage
SYN25_Bus2VTSBlk_GrO_
VTS Bus2 Block
Blocking signal of the voltage
transformer
supervision
function
evaluating the Bus2 voltage
SYN25_SwStA_GrO_
SySwitch Auto
Switching request signal initiated by
the automatic reclosing function
SYN25_CancelA_GrO_
Cancel Auto
Signal to interrupt (cancel) the
automatic switching procedure
SYN25_Blk_GrO_
Block
Blocking signal of the function
SYN25_SwStM_GrO_
SySwitch Manual
Switching request signal initiated by
manual closing
SYN25_CancelM_GrO_
Cancel Manual
Signal to interrupt (cancel) the
manual switching procedure
Table 3-57: The binary input signal of the synchro check / synchro switch function
Binary status signal
Title
Explanation
SYN25_RelA_GrI_
Release Auto
Releasing
the
close
command
initiated by the automatic reclosing
function
SYN25_InProgA_GrI_
SynInProgr Auto
Switching procedure is in progress,
initiated by the automatic reclosing
function
SYN25_UOKA_GrI_
Udiff OK Auto
The voltage difference is appropriate
for automatic closing command
SYN25_FrOKA_GrI_
FreqDiff OK Auto
The
frequency
difference
is
appropriate for automatic closing
command, evaluated for synchro-
check **
SYN25_AngOKA_GrI_
Angle OK Auto
The angle difference is appropriate
for automatic closing command
SYN25_RelM_GrI_
Release Man
Releasing the close command,
initiated by manual closing request
SYN25_InProgM_GrI_
SynInProgr Man
Switching procedure is in progress,
initiated by the manual closing
command
SYN25_UOKM_GrI_
Udiff OK Man
The voltage difference is appropriate
for manual closing command
SYN25_FrOKM_GrI_
FreqDiff OK Man
The
frequency
difference
is
appropriate
for
manual
closing
command, evaluated for synchro-
check **
SYN25_AngOKM_GrI_
Angle OK Man
The angle difference is appropriate
for manual closing command
Table 3-58 The binary output status signals of the synchro check / synchro switch function