Instruction manual
–
AQ F3x0 Feeder protection IED
32 (162
)
Additionally a minimum time delay can be defined by parameter TOC51_MinDel_TPar_ (Min
Time Delay). This delay is valid if it is longer than t(G), defined by the formula above. The
inverse characteristic is valid above G
T
=1,1* G
s
. Above this value the function is guaranteed
to operate.
In following figures the characteristics of IDMT curves are presented with minimum and
maximum pick-up settings in respect of the IED measuring range.
Figure 3-14: IEC Normally Inverse operating curves with minimum and maximum pick up
settings and TMS settings from 0.05 to 20.