140
Options List
Solid State Relay Output, continued
Output Power Supply:
Individually configurable for 0 Vdc, +25 Vdc, or +50 Vdc.
Available Output Sig-
nals:
1 PPS, Programmable Pulse, Locked and Out of Lock.
Pulse Width:
Individually configurable for a fixed, 50 ms pulse, or the
default width of pulse provided by the clock mainframe.
Available Output
1. Dry contact closure.
Configurations:
2. Contact closure to ground.
3. +25/50 Vdc switched for grounded load
4.
+25/50 Vdc with contact closure to ground for non-
grounded load.
See Table B.10.2: Operating Modes of SSR Outputs.
Operating Modes of SSR Outputs
Mode = Dry Contact Closure
1. SSR Output 1
−
Connect load to pins 10 and 11 (polarity not important)
2. SSR Output 2
−
Connect load to pins 14 and 15 (polarity not important)
Mode = Contact Closure to Ground
1. Short pins 9 and 10, connect load to pin 11
2. Short pins 13 and 14, connect load to pin 15
Mode = +25/50 Vdc Switched to Grounded Load
1. Short pins 11 and 12, connect load to pins 9 (
−
) and 10 (+)
2. Short pins 15 and 16, connect load to pins 13 (
−
) and 14 (+)
Mode = +25/50 Vdc Switched to Floating Load
1. Short pins 9 and 10, connect load to pins 11 (
−
) and 12 (+)
2. Short pins 13 and 14, connect load to pins 15 (
−
) and 16 (+)