Page - 30
10. If after 45 seconds, the heat pump displays a "
SMART COMM FAULT
":
A.
Confirm dip switches -
If external controller uses dip switches, confirm switches are in the correct
position. Otherwise, proceed to confirm wiring.
a. Deactivate power to the external controller.
b. Remove access panel on external controller.
c. Check the external controller manual for proper dip switch positioning and confirm dip switches.
d. Reinstall electrical access panel.
e. Reactivate power to the controller.
f. If the fault persists, proceed to confirm wiring.
B.
Confirm wiring -
Confirm wires are oriented properly on the heat pump's "Port B" of the
microprocessor.
a. Deactivate power to heat pump and external controller.
b. Remove the access panel on the heat pump.
c. Reverse wires on "Port B".
d. Reinstall electrical access panel.
7. Reactivate power to the controller.
8. Reactivate power to the heat pump.
C. If fault continues to occur, check with the manufacturer of the external controller for additional advice on
using a heat pump with the controller.
11. After establishing a connection from the external controller to the heat pump, further programming will be
required at the external controller.
l
See external controller manuals or contact installer or manufacturer of that product.
1
-
Ins
ta
ll
at
ion
Summary of Contents for HeatWave SuperQuiet SQ120R
Page 2: ......
Page 28: ...Page 24 Configure Call Flex Enter Installer Menus then proceed 1 Installation ...
Page 33: ...Page 29 Configure for Smart Bus Controller Enter Installer Menus then proceed 1 Installation ...
Page 36: ...Page 32 Configure 2 wire controller Enter Installer Menus then proceed 1 Installation ...
Page 40: ...Page 36 1 Installation ...
Page 41: ...Page 37 Configure for Scheduled Mode Enter Installer Menus then proceed 1 Installation ...
Page 42: ...Page 38 1 Installation ...
Page 45: ...Page 41 1 Installation ...
Page 47: ...Page 43 1 Installation ...
Page 50: ...Page 46 1 Installation ...
Page 53: ...Page 49 1 Installation ...
Page 55: ...Page 51 1 Installation ...
Page 58: ...Page 54 Turbo Boost 1 Installation ...
Page 59: ...Page 55 Set Efficiency Mode to 24 Hour 1 Installation ...
Page 60: ...Page 56 Set Efficiency Mode to Filtration Schedule 1 Installation ...
Page 61: ...Page 57 1 Installation ...
Page 63: ...Page 59 1 Installation ...
Page 65: ...Page 61 1 Installation ...
Page 84: ...Page 80 Model Number Example 3 Appendix ...
Page 89: ......
Page 144: ...Rev L 8 12 13 MASTERTEMP Pool and Spa Heater Installation and User s Guide 55 N TES ...