Minimum and Maximum Operating Voltage
The heat pump must operate within specified voltages.
NOTICE
Failure to heed the following may result in damage to equipment.
l
Operating equipment under higher or lower voltage conditions may result in damage to your compressor, motors
or other electrical components. This damage will not be covered by the product warranty.
1. Measure site voltage. The site voltage
MUST
be measured under “FULL LOAD” conditions. Activate all
equipment using the same electrical panel as the heat pump.
2. If measured site voltage is outside listed ranges, immediately deactivate equipment until site conditions have been
corrected. If unsure of heat pump equipment rating, please
Identifying Model Specifications
Equipment Rating
Minimum
Site Voltage
Maximum
Site Voltage
A Voltage
(208 to 230 Volts)
Single Phase 60 hertz
200 Volts
253 Volts
B Voltage
(208 to 230 Volts)
Three Phase 60 hertz
200 Volts
253 Volts
D Voltage
(380 to 420 Volts)
Three Phase 50 hertz
361 Volts
441 Volts
E Voltage
(380 Volts)
Three Phase 60 hertz
361 Volts
399 Volts
G Voltage
(460 Volts)
Three Phase 60 hertz
437 Volts
483 Volts
H Voltage
(200 to 240 Volts)
Single Phase 50 hertz
180 Volts
264 Volts
1
-
Ins
ta
ll
at
ion
Summary of Contents for HeatWave SuperQuiet SQ120R
Page 2: ......
Page 28: ...Page 24 Configure Call Flex Enter Installer Menus then proceed 1 Installation ...
Page 33: ...Page 29 Configure for Smart Bus Controller Enter Installer Menus then proceed 1 Installation ...
Page 36: ...Page 32 Configure 2 wire controller Enter Installer Menus then proceed 1 Installation ...
Page 40: ...Page 36 1 Installation ...
Page 41: ...Page 37 Configure for Scheduled Mode Enter Installer Menus then proceed 1 Installation ...
Page 42: ...Page 38 1 Installation ...
Page 45: ...Page 41 1 Installation ...
Page 47: ...Page 43 1 Installation ...
Page 50: ...Page 46 1 Installation ...
Page 53: ...Page 49 1 Installation ...
Page 55: ...Page 51 1 Installation ...
Page 58: ...Page 54 Turbo Boost 1 Installation ...
Page 59: ...Page 55 Set Efficiency Mode to 24 Hour 1 Installation ...
Page 60: ...Page 56 Set Efficiency Mode to Filtration Schedule 1 Installation ...
Page 61: ...Page 57 1 Installation ...
Page 63: ...Page 59 1 Installation ...
Page 65: ...Page 61 1 Installation ...
Page 84: ...Page 80 Model Number Example 3 Appendix ...
Page 89: ......
Page 144: ...Rev L 8 12 13 MASTERTEMP Pool and Spa Heater Installation and User s Guide 55 N TES ...