Page - 28
Typically a smart bus controller will have four wires on its smart bus for a heat pump. The
power and ground (usually the 1st and 4th wire) are not used.
Figure 2
Figure 3
5. If dip-switch settings are required, configure them on the external controller now.
DANGER
Failure to heed the following will result in injury or death.
l
Deactivate power to the external controller while setting dip-switches
Example - Jandy AquaLink
®
:
This external controller has dip switches. Confirm they are properly
positioned to operate a heat pump.
l
Set dip-switch "S2" #1 to "ON". The solar option is to be used for the
heat pump.
l
Check Jandy documentation for any further dip switch settings.
6. If additional sensors are required on the external controller, install them on the external controller now.
Example - Pentair EasyTouch
®
and Pentair IntelliTouch
®
:
Some controllers require an additional sensor be connected
to the external controller's power supply circuit board at the
solar connection point. The sensor is not used but will show
an error if not connected.
7. Reinstall electrical access panels on both the heat pump and external controller.
8. Reactivate power to heat pump and external controller.
9. Configure the heat pump to accept external controller signal. See "
Configure for Smart Bus Controller
1
-
Ins
ta
ll
at
ion
Summary of Contents for HeatWave SuperQuiet SQ120R
Page 2: ......
Page 28: ...Page 24 Configure Call Flex Enter Installer Menus then proceed 1 Installation ...
Page 33: ...Page 29 Configure for Smart Bus Controller Enter Installer Menus then proceed 1 Installation ...
Page 36: ...Page 32 Configure 2 wire controller Enter Installer Menus then proceed 1 Installation ...
Page 40: ...Page 36 1 Installation ...
Page 41: ...Page 37 Configure for Scheduled Mode Enter Installer Menus then proceed 1 Installation ...
Page 42: ...Page 38 1 Installation ...
Page 45: ...Page 41 1 Installation ...
Page 47: ...Page 43 1 Installation ...
Page 50: ...Page 46 1 Installation ...
Page 53: ...Page 49 1 Installation ...
Page 55: ...Page 51 1 Installation ...
Page 58: ...Page 54 Turbo Boost 1 Installation ...
Page 59: ...Page 55 Set Efficiency Mode to 24 Hour 1 Installation ...
Page 60: ...Page 56 Set Efficiency Mode to Filtration Schedule 1 Installation ...
Page 61: ...Page 57 1 Installation ...
Page 63: ...Page 59 1 Installation ...
Page 65: ...Page 61 1 Installation ...
Page 84: ...Page 80 Model Number Example 3 Appendix ...
Page 89: ......
Page 144: ...Rev L 8 12 13 MASTERTEMP Pool and Spa Heater Installation and User s Guide 55 N TES ...