Rev. L 8-12-13
MASTERTEMP
®
Pool and Spa Heater Installation and User’s Guide
13
BELOW POOL LEVEL INSTALLATION
If the heater is below water level, the pressure switch must be adjusted. This adjustment must be done by a qualified
service technician. See following
CAUTION
before installation.
CAUTION
BELOW OR ABOVE POOL INSTALLATION
The water pressure switch is set in the factory at 3.00 PSI (± 0.75 PSI). This setting is for a heater installed at pool level.
If the heater is to be installed more than 1’ above or below, the water pressure switch must be adjusted by a qualified
service technician.
See page 35, Figure 29.
FLOW SWITCH
If the heater is installed more than 5’ above the pool or more than 4’ below the pool level, you will be beyond the limits
of the pressure switch and a flow switch must be installed. Locate and install the flow switch externally on the outlet
piping from the heater, as close as possible to the heater. Connect the flow switch wires in place of the water
pressure switch wires.
Section 3. Installation Instructions
VALVES
When any equipment is located below the surface of the pool or spa, valves should be placed in the circulation piping
system to isolate the equipment from the pool or spa. Check valves are recommended to prevent back-siphoning. Back-
siphoning is most likely to occur when the pump stops, creating a pressure-suction differential. Do
NOT
sanitize the pool
by putting chlorine tablets or sticks into the skimmer(s). When the pump is off, this will cause a high concentration of
chlorine to enter the heater, which could cause corrosion damage to the heat exchanger.
CAUTION
Exercise care when installing chemical feeders so as to not allow back siphoning of chemical into the heater, filters
or pump. When chemical feeders are installed in the circulation of the piping system, make sure the feeder outlet line
is down stream of the heater, and is equipped with a positive seal noncorrosive “Check Valve”, (P/N R172288),
between the feeder and heater.
MANUAL BY-PASS
Where the water flow rate exceeds the maximum 120 GPM, a manual
bypass should be installed and adjusted. After installing the valve, adjust
the valve to bring the flow rate within the acceptable range. Then remove
the valve handle or lock it in place to avoid tampering. See
Figure 4
.
Table 1.
See page 46 for Pressure Relief Valve Installations.
l
e
d
o
M
)
M
P
L
(
)
M
P
G
(
.
n
i
M
*
)
M
P
L
(
)
M
P
G
(
.
x
a
M
5
7
1
)
6
7
(
0
2
)
4
5
4
(
0
2
1
0
0
2
)
6
7
(
0
2
)
4
5
4
(
0
2
1
0
5
2
)
5
9
(
5
2
)
4
5
4
(
0
2
1
0
0
3
)
4
1
1
(
0
3
)
4
5
4
(
0
2
1
0
0
4
)
2
5
1
(
0
4
)
4
5
4
(
0
2
1
w
o
lf
d
e
d
n
e
m
m
o
c
e
r
m
u
m
i
x
a
m
e
h
t
d
e
e
c
x
e
t
o
n
o
D
*
.
g
n
i
p
i
p
g
n
it
c
e
n
n
o
c
e
h
t
r
o
f
e
t
a
r
Cool water
Warm water out
Outlet to pool
Inlet to heater
1. Set Manual By-Pass Valve.
2. Remove Handle.
Figure 4.
* Pumps 2 HP or larger can produce water pressure
flow in excess of 120 GPM. For these pumps, a
BY-PASS VALVE is recommended.
Summary of Contents for HeatWave SuperQuiet SQ120R
Page 2: ......
Page 28: ...Page 24 Configure Call Flex Enter Installer Menus then proceed 1 Installation ...
Page 33: ...Page 29 Configure for Smart Bus Controller Enter Installer Menus then proceed 1 Installation ...
Page 36: ...Page 32 Configure 2 wire controller Enter Installer Menus then proceed 1 Installation ...
Page 40: ...Page 36 1 Installation ...
Page 41: ...Page 37 Configure for Scheduled Mode Enter Installer Menus then proceed 1 Installation ...
Page 42: ...Page 38 1 Installation ...
Page 45: ...Page 41 1 Installation ...
Page 47: ...Page 43 1 Installation ...
Page 50: ...Page 46 1 Installation ...
Page 53: ...Page 49 1 Installation ...
Page 55: ...Page 51 1 Installation ...
Page 58: ...Page 54 Turbo Boost 1 Installation ...
Page 59: ...Page 55 Set Efficiency Mode to 24 Hour 1 Installation ...
Page 60: ...Page 56 Set Efficiency Mode to Filtration Schedule 1 Installation ...
Page 61: ...Page 57 1 Installation ...
Page 63: ...Page 59 1 Installation ...
Page 65: ...Page 61 1 Installation ...
Page 84: ...Page 80 Model Number Example 3 Appendix ...
Page 89: ......
Page 144: ...Rev L 8 12 13 MASTERTEMP Pool and Spa Heater Installation and User s Guide 55 N TES ...