6. ENCLOSURE DIMENSIONS AND INSTALLATION DATA
Enclosure type
panel, Incabox XT L57
Material
self-extinguishing NORYL 94V-0,
polycarbonate
Enclosure dimensions
96 x 96 x 79 mm
Panel window
92 x 89 mm
Fixing methods
grips on the side of the enclosure
Conductor cross-sections
(
separable connectors)
2.5 mm
2
(supply and alarm outputs),
1.5 mm
2
(others)
7. DESCRIPTION OF TERMINAL STRIPS AND ELECTRICAL CONNECTIONS
The numbering, location, and description of the connections on the back panel and the method of connecting
sensors and electrical signals:
a)
measurement connections (RTD, TC, mA, V, mV, R), INPUT1÷ INPUT4; the parameters configuration is described
in chapter 12.3
a.1)
connection of the 2- and 3-wire transducer (Iou – output current, Uou – output voltage)
b)
connections of the optional analogue output module (OUTPUT5÷OUTPUT8) and of functional binary inputs
(BIN1÷BIN5); the parameters configuration is described in chapter 12.4
Terminal clamps
(connections)
Description
IN1-IN2-IN3
RTD and R (Pt100, Pt500, Pt1000, Ni100, 850Ω) inputs, in a 2- and 3-wire connection
IN1-IN2
thermocouple input TC (J, K, S, B, R, T, E, N) and voltage input 0÷60 mV
IN1-GND
current input 0/4÷20 mA
IN2-GND
voltage input 0÷10 V
+24 V
24 V (in relation to the GND) of the integrated power supply of field transducers