12.3. CONFIGURATION OF MEASUREMENT INPUTS
The controller has 4 universal measurement inputs for connecting temperature sensors and electrical signals.
Table 12.3. Configuration parameters in the
Measurement inputs configuration
menu for the selected input
(numbers 1
÷
4)
Parameter
Range of variability of the parameter and description
Default
settings
Input type
Off
the measurement input is absent in the presentation and in
the recording
Pt100
thermoresistance sensor (RTD) Pt100 (-200 ÷ 850°C)
Pt100
Pt500
thermoresistance sensor (RTD) Pt500 (-200 ÷ 620°C)
Pt1000
thermoresistance sensor (RTD) Pt1000 (-200 ÷ 620°C)
Ni100
thermoresistance sensor (RTD) Ni100 (-50 ÷ 170°C)
J
(Fe-CuNi)
thermoelectric sensor (thermocouple) type J (-40 ÷ 800°C)
K
(NiCr-NiAl)
thermoelectric sensor (thermocouple) type K (-40 ÷ 1,200°C)
S
(PtRh 10-Pt)
thermoelectric sensor (thermocouple) type S (-40 ÷ 1,600°C)
B
(PtRh30PtRh6)
thermoelectric sensor (thermocouple) type B (-300 ÷ 1,800°C)
R
(PtRh13-Pt)
thermoelectric sensor (thermocouple) type R (-40 ÷ 1,600°C)
T
(Cu-CuNi)
thermoelectric sensor (thermocouple) type T (-25 ÷ 350°C)
E
(NiCr-CuNi)
thermoelectric sensor (thermocouple) type E (-25 ÷ 850°C)
N
(NiCrSi-NiSi)
thermoelectric sensor (thermocouple) type N (-35÷ 1,300°C)
4÷20 mA
current signal 4...20 mA
0÷20 mA
current signal 0...20 mA
0÷10 V
voltage signal 0...10 V
0÷60 mV
voltage signal 0...60 mV
0÷850 Ω
resistance signal 0...850 Ω
Line resistance
(1)
0.00
÷
50.00 Ω
total resistance of leads for 2-wire RTD sensors and 850 Ω
0.00 Ω
Thermocouple
cold tip
temperature
Auto
0.1÷ 60.0 °C
automatic or constant compensation of temperature of the
cold junction of thermocouples,
Auto
=
0.0°C
Auto
Decimal dot
position/resolution
None
0, no point
(2)
or resolution 1 °C for temperature
Position 1
(0.1
°C
)
Position 1
0.0
(2)
or resolution 0.1 °C for temperature
Position 2
0.00
(2)
Position 3
0.000
(2)
Start of the input scale
-199.9
÷
1999.9 °C
or
-9999
÷
19999
units
(2)
– indication for 0 mA, 4 mA, 0 V,
2 V, 0 mV, 0 Ω - start of the input scale
-100.0 °C
End of the input scale
-199.9
÷
1999.9 °C
or
-9999
÷
19999
units
(2)
– indication form 20 mA, 10 V,
60 mV, 850 Ω - end of the input scale
800.0 °C
Filtration
(3)
1
÷
10
digital filtration of measurements (response time)
1
Offset calibration
zero offset:
-50.0
÷
50.0 °C
or
-500
÷
500
units
(2)
0.0 °C
Slope calibration
sensitivity (gain):
85.0
÷
115.0 %
100.0 %
Notes: (1)
- in the case of 3-wire sensors, the
Line resistance
parameter must be equal to
0.00 Ω
(automatic compensation)
(2)
- applies to analogue inputs (mA, V, mV, Ω)
(3)
- in the case of
FiLtration
=
1
the response time is equal to 1 s, in the case of
FiLtration
=
10
it is equal to at
least 2.5 s. Higher degree of filtration means a "smoother" measured value and a longer response time, which
is recommended in the case turbulent measurements (e.g. water temperature in the boiler without an agitator)