22
PID selection for SP1 and
SP=IN
None (ON-OFF)
– control/alarm of the
ON-OFF type with hysteresis
assignment of a set of PID parameters
to the
Set point value SP1
and to the
Setpoint value SP
taken from
input
IN
when the measurement is smaller than
or equal to the
SP1
value (SP=IN and
SP≤SP1), so-called
gain scheduling
None (ON-
OFF)
Set of PID1
÷
PID8 parameters
-
control of the PID type, chapter 12.4.2
Setpoint/Alarm value SP2 -999.9
÷
9999.9°C
or
-9999
÷
99999
units
(1)
– setpoint value 2
50.0 °C
Hysteresis H2
0
÷
500.0°C
or
0
÷
5000
units
(1)
- hysteresis 2 or tuning zone PID (chapt. 12.4.2.2)
1.0 °C
PID Selection for SP2
and SP=IN
None (ON-OFF)
– control/alarm of the
ON-OFF type with hysteresis
assignment of a set of PID parameters
to
Set point value SP2
and to
Set point
value SP
taken from
input IN
when the
measurement is larger than the
SP1
value
(SP=IN and SP>SP1), so-called
gain scheduling
None (ON-
OFF)
Set of PID1
÷
PID8 parameters
-
control of the PID type, chapter 12.4.2
Autotuning of PID
parameters
(a description can be
found in chapter 12.4.2.2)
Disabled
selection of the PID parameters
selection algorithm (autotuning), the
calculated data is saved in the
Set of
PID parameters
related to the
Selected
setpoint value SP
for the current output
Disabled
Automatic selection (continuous mode)
Step response method (quick)
Oscillation method (slower)
Set point value for the
manual mode
0
÷
100
%
1% step
control value for outputs in the manual mode (open control
loop), chapter 12.4.1.3
50 %
Pulsing period for the
manual mode
1
÷
360
sec.
applies only to bistate outputs (P/SSR), in the case of
analogue outputs (mA/V), the parameter is insignificant,
chapter 12.4.1.3
5 sec.
Output emergency state
No change
status of the control/alarm outputs if
the measurement range of the control
signal is exceeded or in the case of a
failure/error of a sensor/measurement
module, chapter 15
No change
OFF state (MV=0%)
ON state (MV=100%)
Manual mode with a set value
State of control after
power up
Disabled (Stop)
Enabled (Start)
No change (Start or
Stop)
No change
Control time
(with the possibility of
manual control using the
[Start]
/
[Stop]
,
[F]
, and
[F1]
buttons - chapter 10,
and function inputs
BIN
,
chapter 7b)
Continuous
constantly enabled control
Continuous
Limited by
date and time
recording is active within the range of the
Date
and the
Time
defined by the parameters
Start
and
End of time
control
Periodic
daily (hourly)
hourly control is active within the range of the
Time
defined
by the parameters
Start
and
End of time control
Start of control time
Date
:
01.06.2008
÷
31.12.2099
,
Time
:
00:00:00
÷
23:59:59
, the parameters are active when
Control time
=
Date and time limited
or
Periodic daily (hourly)
2013.06.01
00:00:00
End of control time
Alarm sound signal
Disabled
signalling of enabling of the P/SSR output with a built-in
buzzer. The alarm can also be controlled from the level of the
[F]
function button, chapter 10, item c.
Disabled
Enabled
E-mail alarm
notifications
Disabled
a service that enables signalling of enabling of the P/SSR
output via an email message; a description can be found in
chapter 12.4.1.4
Disabled
Enabled
F1 button and BIN input
function
None
applies to the P/SSR and mA/V output
when it is present and the parameter
Analogue output (mA/V)
function
=
Control
, the
BIN
input always has a
higher priority than the
[F1]
button
None
Selection of the setpoint SP (SP1/SP2)
Manual mode for outputs
(Auto/Manu)
Start/Stop control