18
Table 12.2. Configuration parameters in the
Display channel configuration
menu for the selected channel (1
÷
4)
Parameter
Range of variability of the parameter and description
Default
settings
Name, unit and group
edition of the name of the channel and the group (max. length 16 characters)
and of the measurement unit (4 characters) is possible on the computer (via the
USB port or the Ethernet and the ARSOFT-CFG-WZ1 software or by copying the
configuration - chapter 12.9). The format of a single section in the
AR654.txt
file is
the following:
[Chan1] Name=
Channel 1
, Unit=
°C
, [
Group1]
Name
=
Group 1
Channel i
(for
i=1÷4),
°C,
Group j (
for
j=1÷4
)
Measured value to be
displayed
None
- the measurement channel is absent in the presentation and in the recording
Measurement
from the input
IN i
(for
i=1÷4)
Measurement from the input IN1
Average (IN1+IN2+IN3)/3
Measurement from the input IN2
Average (IN1+IN2+IN3+IN4)
Measurement from the input IN3
The largest of the measurements IN1
and IN2
Measurement from the input IN4
The largest of the measurements IN3
and IN4
Difference between the
measurements IN1-IN2
The largest of the measurements IN1,
IN2, and IN3
Difference between the
measurements IN3-IN4
The largest of the measurements IN1,
IN2, IN3, and IN4
Difference between the
measurements IN1-IN2-IN3
The smallest of the measurements
IN1 and IN2
The difference IN1-IN2-IN3-IN4
The smallest of the measurements
IN3 and IN4
Sum of the measurements IN1+IN2
The smallest of the measurements
IN1, IN2, and IN3
Sum of the measurements IN3+IN4
The smallest of IN1,IN2,IN3,IN4
Sum of the measurements IN1+IN2+IN3 (IN1+IN2)/2 - (IN3+IN4)/2
Sum of IN1+IN2+IN3+IN4
The ratio of the measurements IN1/IN2
Average (IN1+IN2)/2
The ratio of the measurements IN3/IN4
Average of the measurements
(IN3+IN4)/2
Assigned and active
outputs
the numbers (
1
÷
4
or
None
) of the control/alarm outputs are displayed for
which the same type of
control signal
was assigned as the
Measured value
of
the current display channel, chapter 12.4.1, when
None
for the output is not
related or switched off (the parameter
Control type
=
Off
)
1
÷
4
Bottom range for
graphics and SP
-999.9
÷
9999.9°C
or
-9999
÷
99999
units
(1)
– the lower value of the range of
variability for graphic elements (bar graph, counter, diagram) and for the
setpoint values SP of the related control outputs (1÷8)
-100.0 °C
Top range for graphics
and SP
-999.9
÷
9999.9°C
or
-9999
÷
99999
units
(1)
– the upper value of the range of
variability for graphic elements (bar graph, counter, diagram) and for the
setpoint values SP of the related control outputs (1÷8)
800.0 °C
Assignment of the
measurement group
channel
Belongs to all
groups or only to one group in the range of
1
÷
4
,
channel grouping is used in the measurement presentation modes
Group i
(for
i=1÷4)
Background colour
selection of the background colour in the measurement presentation modes,
23 colours are available
colour
Notes: (1)
- applies to analogue inputs (mA, V, mV, Ω)