Configuration parameters for the measurement channel of the display numbered
KP
= 0 ÷ 3, 0=channel 1, 3=channel 4, chapter 12.2
0x7E + KP *7
0 ÷ 27
Parameter
Measured value
to be displayed
(chapter 12.2)
R/W
0x7F + KP *7
-9999 ÷ 99999
Parameter
Bottom range for graphics and SP
, 2 registers, 32-bit value
R/W
0x81 + KP *7
-9999 ÷ 99999
Parameter
Top range for graphics and SP
, 2 registers, 32-bit value
R/W
0x83 + KP *7
0 ÷ 3
Parameter
Assignment of measurement group
R/W
0x84 + KP *7
0 ÷ 22
Parameter
Background colour
R/W
Configuration parameters for control output with the number
WY
= 0 ÷ 3, 0=output 1, 3=output 4, chapter 12.4.1
0x9A + WY *32
0 ÷ 31
Parameter
Assignment of control signal
(chapter 12.4.1)
R/W
0x9B + WY*32
0 ÷ 5
Parameter
Type of control/alarm
R/W
0x9C + WY*32
0 ÷ 11
Parameter
Setpoint value (SP) selection
R/W
0x9D + WY*32
0 ÷ 3
Parameter
Output emergency state
R/W
0x9E + WY*32
0 ÷ 5000
Parameter
Hysteresis H1
R/W
0x9F + WY*32
-9999 ÷ 99999
Parameter
Setpoint/Alarm value SP1
, 2 registers, 32-bit value
R/W
0xA1 + WY*32
0 ÷ 8
Parameter
PID selection for SP1 and SP=IN
R/W
0xA2 + WY*32
0 ÷ 5000
Parameter
Hysteresis H2
R/W
0xA3 + WY*32
-9999 ÷ 99999
Parameter
Setpoint/Alarm value SP2
, 2 registers, 32-bit value
R/W
0xA5 + WY*32
0 ÷ 8
Parameter
PID selection for SP2 and SP=IN
R/W
0xA6 + WY*32
0 ÷ 3
Parameter
Autotuning of PID parameters
R/W
0xA7 + WY*32
0 ÷ 100
Parameter
Setpoint value for manual mode
R/W
0xA8 + WY*32
1 ÷ 360
Parameter
Pulsing period of manual mode
R/W
0xA9 + WY*32
0 ÷ 2
Parameter
State of control after power up
R/W
0xAA + WY*32
0 ÷ 2
Parameter
Control time
R/W
0xAB + WY*32
0x0101 ÷ 0x630C
years (HB) and months (LB)
Parameter
Start of control time
R/W
0xAC + WY*32
0x0100 ÷ 0x1F17
days (HB) and hours (LB)
R/W
0xAD + WY*32
0x0000 ÷ 0x3B3B
minutes (HB) and seconds (LB)
R/W
0xAE + WY*32
0x0101 ÷ 0x630C
years (HB) and months (LB)
Parameter
End of control time
R/W
0xAF + WY*32
0x0100 ÷ 0x1F17
days (HB) and hours (LB)
R/W
0xB0 + WY*32
0x0000 ÷ 0x3B3B
minutes (HB) and seconds (LB)
R/W
0xB1 + WY*32
0 ÷ 1
Parameter
Alarm sound signal
R/W
0xB2 + WY*32
0 ÷ 1
Parameter
Email alarm notifications
R/W
0xB3 + WY*32
0 ÷ 3
Parameter
F1 button and BIN input function
R/W
0xB4 + WY*32
0 ÷ 3
Parameter
Analogue output (mA/V) function
R/W
0xB5 + WY*32
0 ÷ 3
Parameter
Output (mA/V) and standard selection
R/W
0xB6 + WY*32
-9999 ÷ 99999
Parameter
Start of retransmission scale (mA/V)
, 2 registers, 32-bit value
R/W
0xB8 + WY*32
-9999 ÷ 99999
Parameter
End of retransmission scale (mA/V)
, 2 registers, 32-bit value
R/W
Configuration parameters of PID set number
ZP
= 0÷7, 0=set 1, 7=set 8, chapter 12.4.2
0x11A + ZP *4
1 ÷ 18000
Parameter
Proportional band Pb
(chapter 12.4.2)
R/W
0x11B + ZP *4
0 ÷ 3,600
Parameter
Integration time constant Ti
R/W
0x11C + ZP *4
0÷999
Parameter
Differentiation time constant Td
R/W
0x11D + ZP *4
3 ÷ 360
Parameter
Pulsing period Tc for the output
R/W
0x13A (314)
0 ÷ 6
Parameter
F button funtion
(chapter 12.9)
R/W
0x13B (315)
0 ÷ 1
Parameter
BIN5 input
funtion
(chapter 12.9)
R/W
0x13C (316)
0 ÷ 1
Parameter
Buttons and touch sounds
(chapter 12.9)
R/W
0x13D (317)
0 ÷ 3
Parameter
Password protection
(chapter 12.9)
R/W
0x13E (318)
0 ÷ 9,999
Parameter
Administrator assess
password
(chapter 12.9)
R/W