Control/alarm type
(applies to each type of
control: ON-OFF with
hysteresis, PID, and
program)
Off
constantly switched off output
Disabled
Inverted
/heating
Fig. 12.4.1.1. Characteristics of the
Heating
type (for ON-OFF)
Direct/cooling
Fig. 12.4.1.2. Characteristics of the
Cooling
type (for ON-OFF)
Inside of the
band
(
only
alarm
, not
available for
control of the
PID type and
program
control)
Fig.12.4.1.3. Characteristics of an
Inside of the band
alarm (ON-OFF)
Outside of the
band
(only
alarm
, not
available for
control of the
PID type and
program
control
)
Fig.12.4.1.4. Characteristics of an
Outside of the band
alarm (ON-OFF)
Manual
mode
the output works in the manual mode controlled with the
parameters
Setpoint value for the manual mode
and
Pulsing
period for the manual mode
(described further in this table)
Setpoint value (SP)
selection
Setpoint/alarm value SP1
– applies to
SP1
and
H1
from the current output
Set/alarm
value SP1
Setpoint/alarm value SP2
– applies to
SP2
and
H2
from the current output
Measurement from input IN1
÷
Measurement from input IN4
Setpoint value SP from Program 1
÷
Setpoint value SP from Program 4
–
assignment of program control to the current output, chapter 12.4.3
Selected value SP from Output 1
– both
SP
and
Hysteresis
and
Selection
of PID parameters for SP
are common and taken from the 1st output
SP from Output 1 + actual SP1
(SP1 as an offset for 3-way control)
Setpoint/Alarm value SP1 -999.9
÷
9999.9°C
or
-9999
÷
99999
units
(1)
– setpoint value 1
50.0 °C
Hysteresis H1
0
÷
500.0°C
or
0
÷
5000
units
(1)
- hysteresis 1 or tuning zone PID (chapt. 12.4.2.2)
1.0 °C