Opening Compensation According to Temperature or Static
Pressure: How it Works
Temperature compensation
The inlet temperature compensation is expressed as a percentage per degree difference between the
average controller temperature and the average reading of the probes assigned to the inlet. It determines
by how much the inlet must open or close to help reduce the temperature differences in the building. For
each degree above or below the average temperature, the inlet will open or close using the compensation
value assigned by the user. For example, if the compensation value is set to 2%/°F and the inlet's probes
read 3°F above the average controller temperature, the inlet will open 6% to help decrease the tempera-
ture in that zone. The maximum temperature compensation value is 10%.
Static pressure compensation
The static pressure compensation is expressed as a percentage per 0.01inch of water (%/0.01"WC). It
determines by how much the inlet must open or close to help reduce or enhance the static pressure in the
building according to set points. For each .01"WC above the high static pressure set point or below the
low static pressure set point, the inlet will open or close using the compensation value assigned by the
user. For example, if the compensation value is set to 1%/"WC and the static pressure is 0.05"WC above
the high static pressure set point, the inlet will open of 5% to help decrease the static pressure in the
building. The maximum static pressure compensation value is 10%.
Setting the Temperature and Static Pressure Compensation
1. Using the menu select arrow keys, navigate to
Inlet→Compensation→Temp & Static
.
This menu is accessible if the inlet is enabled.
2. Set the Temperature compensation to the desired value.
3. Set the static pressure compensation to the desired value.
This parameter is accessible if the static pressure sensor is used.
Selecting the Static Pressure Compensation Stages
1. Using the menu select arrow keys, navigate to
Inlet→Compensation→Static Stages
.
This menu is accessible if the inlet is enabled and the static pressure sensor is enabled.
2. Put a checkmark beneath the fan stages on which the static pressure compensation is applied.
Setting the Static Pressure Setpoints
When the high pressure set point is reached, the inlet opens to the static pressure compensation value; it
closes by the same amount when the low pressure level is reached. The static pressure high and low set-
points can be adjusted from 0 to 0.2 inches of water.
1. Using the menu select arrow keys, navigate to
Inlet→Stat pressure
.
This menu is accessible if the inlet is enabled and if the static pressure sensor is used.
2. Set the high and low static pressure setpoints to the desired value.
890-00081
Expert VT-110
45
Summary of Contents for Expert VT-110
Page 1: ...Expert VT 110 User Manual 890 00081 Version 24 REV 19...
Page 6: ...NOTES 6 890 00081 Expert VT 110...
Page 10: ...NOTES 10 890 00081 Expert VT 110...
Page 12: ...NOTES 12 890 00081 Expert VT 110...
Page 22: ...NOTES 22 890 00081 Expert VT 110...
Page 26: ...NOTES 26 890 00081 Expert VT 110...
Page 32: ...NOTES 32 890 00081 Expert VT 110...
Page 46: ...NOTES 46 890 00081 Expert VT 110...
Page 50: ...Chapter 13 Stir Fan 50 890 00081 Expert VT 110...
Page 52: ...NOTES 52 890 00081 Expert VT 110...
Page 64: ...NOTES 64 890 00081 Expert VT 110...
Page 76: ...NOTES 76 890 00081 Expert VT 110...
Page 78: ...NOTES 78 890 00081 Expert VT 110...
Page 79: ...A Worksheets 890 00081 Expert VT 110 79...
Page 80: ...Appendix A Worksheets 80 890 00081 Expert VT 110...
Page 81: ...Appendix A Worksheets 890 00081 Expert VT 110 81...