15
Relative Humidity
Compensation
Topics Covered in this Chapter
Relative Humidity Compensation: How it Works
Setting the Relative Humidity Compensation Parameters
Relative Humidity Compensation: How it Works
The controller offers different ways to compensate for high/low relative humidity (RH) levels in the room.
High RH compensation with the heating outputs
The controller can compensate for high humidity levels by activating the heaters in timer mode. As the
RH level increases, the controller increases the “On Time” portion of the heating timer to compensate for
the change. The maximum compensated heating Max “On Time” is reached when the RH level is 10%
above the RH Set Point.
RH heat timer
The RH heat timer is composed of an “On Time” and of a “Cycle Time”. The heaters run during the “On
Time” and then stop until the end of the “Cycle Time”. The “On Time” portion of this cycle increases as the
RH level increases.
890-00081
Expert VT-110
61
Summary of Contents for Expert VT-110
Page 1: ...Expert VT 110 User Manual 890 00081 Version 24 REV 19...
Page 6: ...NOTES 6 890 00081 Expert VT 110...
Page 10: ...NOTES 10 890 00081 Expert VT 110...
Page 12: ...NOTES 12 890 00081 Expert VT 110...
Page 22: ...NOTES 22 890 00081 Expert VT 110...
Page 26: ...NOTES 26 890 00081 Expert VT 110...
Page 32: ...NOTES 32 890 00081 Expert VT 110...
Page 46: ...NOTES 46 890 00081 Expert VT 110...
Page 50: ...Chapter 13 Stir Fan 50 890 00081 Expert VT 110...
Page 52: ...NOTES 52 890 00081 Expert VT 110...
Page 64: ...NOTES 64 890 00081 Expert VT 110...
Page 76: ...NOTES 76 890 00081 Expert VT 110...
Page 78: ...NOTES 78 890 00081 Expert VT 110...
Page 79: ...A Worksheets 890 00081 Expert VT 110 79...
Page 80: ...Appendix A Worksheets 80 890 00081 Expert VT 110...
Page 81: ...Appendix A Worksheets 890 00081 Expert VT 110 81...