GASGUARD IS CONTROLLER Issue: R2, Date: 26/09/2011, CRN: 7502
Page 55
Channel 1
Gas
CH4
Range
5% v/v
Verified
mA / V
Engineering Value
Sensor Input Type
4-20mA
Apply minimum range to channel, zero if necessary
4mA
0.00 (-0.02 – 0.02)
Channel Delay
1s Delay
Apply maximum to channel, adjust span if required
20mA
5.00 (4.95 – 5.05)
Programmed
Setpoint
Test Values
┌─ Relays
─┐
Engineering Value V
Action
iMAC
Operation
1
2
3
4
Low Fault
2mA
2.0mA
Falling
Latching
Fault LED
Programmed
Values
(1.98 - 2.02)
Verified on Test
Alarm 1
1.00%
7.2mA
Rising
Non-Latching
Alarm LED
Programmed
Values
(7.13 -7.27 )
Verified on Test
Alarm 2
1.50%
8.8mA
Rising
Non-Latching
Alarm LED
Programmed
Values
(8.71 - 8.89)
Verified on Test
Alarm 3
2.00%
10.4mA
Rising
Latching
Alarm LED
Programmed
Values
(10.3 - 10.5)
Verified on Test
High Fault
22mA
22mA
Rising
Latching
Fault LED
Programmed
Values
(21.8 – 22.2)
Verified on Test
Summary of Contents for gasguard
Page 47: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 46 ...
Page 62: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 61 B2 Main Menu Flowchart ...
Page 63: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 62 B3 Calibration Flowchart ...
Page 64: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 63 B4 Configuration Flowchart ...
Page 74: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 73 Appendix C Approvals ...
Page 75: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 74 ...
Page 76: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 75 ...
Page 77: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 76 ...
Page 78: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 77 ...
Page 79: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 78 ...