GASGUARD IS CONTROLLER Issue: R2, Date: 26/09/2011, CRN: 7502
Page 14
Example 4:
Inclusion of a relay across two Zone Blocks. Vote counts set to allow basic alarm logic decoding.
Assume set-points and relay inclusions not shown, to be set as [ NOT IN ].
RELAY 1:
Status [ ON ]
Zn1 [ IN ]
Allocate Relay 1 to Zone Block 1.
Zn2 [ IN ]
Also allocate Relay 1 to Zone Block 2.
ZONE 1:
Status [ ON ]
Ch1 A1 [ IN ]
(include Chan 1 A1 set-point )
Ch2 A1 [ IN ]
(include Chan 2 A1 set-point )
Voting [ 2 ]
ZONE 2:
Status [ ON ]
Ch3 A2 [ IN ]
(include Chan 3 A2 set-point )
Voting [ 1 ]
Relay 1 will become active when:- Ch1 A1 is active AND CH2 A1 is active, OR Ch3 A2 is active.