Decimal Point
Each Input channel may have its display reading configured to correctly indicate the process value.
The available settings for decimal places are:-
•
nnnn (e.g. 2500)
•
nnn (e.g. 250)
•
nn.n (e.g. 25.0)
•
n.nn (e.g. 2.50)
Full Scale Reading
Input process signals to the controller are typically in the range 4 – 20mA and as such may represent a variety of
actual process scaling. To set the relationship between 4-20mA input and the process scaling, the channel full scale
value may be set. Settings are per digit, with up to four digits available. The displayed value of this setting will
depend on the decimal place setting.
The maximum value that may be set is to be 9999 (999 / 99.9 / 9.99 depending on decimal point position)
Units
The process displayed readings can be given units of measurement indicator. There are ten pre-set unit types
available for selection, namely:-
•
%v/v (percent volume per volume)
•
ppm (parts per million)
•
LEL (Lower Explosive Limit)
•
% (percent)
•
V (volts)
•
mV (millivolts)
•
rpm (revolutions per minute)
•
Hz (cycles per second)
•
kHz (thousands of cycles per second)
•
m/s (meters per second)
Tag
A channel may be given an identification name that provides meaningful representation of its purpose/function within
a system. The tag input is entered as a 9 character name consisting of the following characters:-
•
Symbols: blank * - + .
•
Numeric: 0 – 9
•
Alpha A-Z (uppercase only)
Summary of Contents for gasguard
Page 47: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 46 ...
Page 62: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 61 B2 Main Menu Flowchart ...
Page 63: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 62 B3 Calibration Flowchart ...
Page 64: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 63 B4 Configuration Flowchart ...
Page 74: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 73 Appendix C Approvals ...
Page 75: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 74 ...
Page 76: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 75 ...
Page 77: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 76 ...
Page 78: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 77 ...
Page 79: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 78 ...