Chapter 4 Parameter Index
http://www.acdrive-china.com
88
P5: PLC Operating
Function
code
Function
Name
LCD
Display
Range of settings
Default
Change
MODBUS
Address
P5.00
PLC
Operating
mode
PLC
Operating
mode
0: Single cycle 1
1: Single cycle 2
(holding final
value)
2: Continuous
operation
2
× 0600
P5.01
PLC
restarting
mode
selection
PLC
restarting
mode
selection
0: Restart from first
step
1: Continue from
the step where
the ac drive stops
2: Continue to
operate at the
frequency when
the ac drive stops
0
× 0601
P5.02
Saving
PLC status
when
power off
Save PLC
status
when
power off
0: Not save
1: Save
0
× 0602
P5.03
Unit of
step time
Unit of
step time
0: Second
1: Minute
0
× 0603
P5.04
Program
Operating
Timing T1
Program
Operating
Time 1
0.1~3600 10.0
○
0604